ABB 2TFH100682R1001 Moulded Case Circuit Breaker - IEC60947-2

Manufacturer
ABB
Part number
2TFH100682R1001

Quick Summary

ABB 2TFH100682R1001 is a moulded case circuit breaker that protects industrial power distribution. In demanding environments, mis-sizing or nuisance trips can cause costly downtime. Certified to IEC60947-2 and CE with RoHS compliance, this XT2 device aligns with global safety and sustainability standards. Designed for easy plug-in installation within the ABB SACE Tmax XT ecosystem, it delivers reliable interruption performance in compact panel layouts. With 3P protection and high breaking capacity, it supports scalable protection across small blocks to critical motor feeders while reducing maintenance and lifecycle cost. This combination of durability and compliance translates to reduced spare parts, faster commissioning, and predictable, safer operation.

Product Information

Extended Description

2TFH100682R1001 ABB: XT2H160 TMA100/1000 PMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 9.5 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB 2TFH100682R1001 is a three-pole moulded case circuit breaker rated at 100 A for applications up to 690 V AC or 500 V DC. This rating enables safe protection across mixed supply environments and supports compact, modular panel designs used in modern factories. Key performance feature is the high breaking capacity: Ics up to 100 kA and Icu up to 100 kA depending on voltage, with an 8 kV rated impulse withstand. These figures translate into reliable fault interruption, even in high transient fault scenarios, reducing equipment damage and downtime. Release type TM/TMA offers targeted tripping for selective protection in ABB Tmax XT ecosystems. This supports streamlined panel design and easy retrofit without extensive wiring changes. Durability is robust: electrical durability is 8000 cycles (120 cycles per hour) and mechanical durability is 25000 cycles (240 cycles per hour). This longevity lowers maintenance costs and improves total cost of ownership. Compliance and environmental data streamline global deployments: RoHS, REACH, CMRT declarations simplify regulatory approvals across regions, while IEC60947-2 conformance aligns with international standards. The plug-in terminal connection type supports quick installation and field replacement within the SACE Tmax XT family.

Get a Quick Quote for a ABB 2TFH100682R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100682R1001? Enquire Now

FAQs

This unit uses plug-in circuit-breaker terminals designed for quick field replacement within ABB Tmax XT assemblies. Ensure a compatible 3P panel frame, verify rated voltage (690 VAC / 500 V DC capability) and confirm alignment with the SACE Tmax XT family for seamless panel fit and reliable conductors routing. Tighten terminal screws to the manufacturer’s torque specification and perform a functional check after installation.
Key ratings include rated current In of 100 A, rated insulation voltage Ui of 1000 V, rated operational voltage Ue of 690 V AC / 500 V DC, rated impulse withstand voltage Uimp of 8 kV, and short-circuit capabilities with Ics up to 100 kA and Icu up to 100 kA depending on voltage. Electrical durability is 8000 cycles (120/h) and mechanical durability is 25000 cycles (240/h).
Yes. With three poles, 100 A rating, and high breaking capacity, the device is well-suited for motor feeders, distribution boards, and switchgear in industrial settings. Its compatibility with the SACE Tmax XT ecosystem supports selective tripping and coordinated protection in motor control centers and panel boards.
The unit complies with IEC 60947-2 and GB/T 14028.2, presents CE conformity, RoHS compliance, and REACH declarations. CMRT reporting is available, and WEEE category information is provided to support regional regulatory requirements and responsible end-of-life handling.
Durability specs (8000 electrical cycles, 25000 mechanical cycles) mean longer service life and fewer replacement trips, reducing maintenance costs and downtime. Its plug-in design accelerates commissioning and field replacements, improving overall return on investment in capital projects and ongoing operations.