ABB XT2H160 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 2TFH102013R1001
Manufacturer
ABB
Part number
2TFH102013R1001

Quick Summary

XT2H160 Moulded Case Circuit Breaker from ABB provides reliable overcurrent protection for low-voltage distribution panels and equipment. In dense switchgear environments, nuisance trips and unplanned downtime can disrupt production; a robust MCCB like this helps stabilize fault response and simplify maintenance. It aligns with IEC 60947-2, CE declarations, and RoHS/REACH compliance, reinforcing regulatory confidence across the supply chain. Designed for 3P systems and compact panel layouts, it delivers predictable protection, easy installation, and favorable lifecycle costs, while integrating with ABB’s SACE Tmax XT family for streamlined spare parts and service support.

Product Information

Extended Description

2TFH102013R1001 ABB: XT2H160 Ekip LS/I R10 WMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.32 kg
Package Level 1 Width
287 mm
Package Level 1 Height
230 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Gross Weight
3.42 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LS/I
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Three-pole, 690 V AC operation with a rated current of 10 A. Business Impact: Enables safe protection for small-to-medium feeders with minimal voltage drop and reliable trip performance. Application: Control panels and distribution boards in manufacturing lines. The design supports quick integration into existing 3P switchgear and reduces engineering time during panel updates. Feature: High short-circuit withstand capability with Ics up to 100 kA at 220–240 V and 70–65 kA at higher voltages. Business Impact: Maximizes system safety during fault events, lowering the risk of equipment damage and fire. Application: Motor feeders and power distribution where fault currents may spike. Feature: Rated operational voltage of 690 V AC and rated insulation 1000 V. Business Impact: Provides a broad voltage margin for diverse industrial applications, simplifying device selection across multiple panels. Application: LV distribution in warehouses, process lines, and automation cabinets. Feature: Electrical durability 8000 cycles and mechanical durability 25000 cycles. Business Impact: Extends service life in frequent switching environments, reducing maintenance intervals and total cost of ownership. Application: Automation and packaging lines with frequent on/off cycling. Feature: Withdrawable terminal connection type and compact footprint (90 mm width, 130 mm height, 82.5 mm depth; 3.32 kg). Business Impact: Enhances safety during maintenance and saves cabinet space; eases retrofits in limited-bay enclosures. Application: Modernization projects and retrofit of legacy MCCBs in existing switchgear. Feature: RoHS and REACH declarations with CE conformity. Business Impact: Ensures regulatory compliance and supply chain integrity, supporting sustainability goals and risk management. Application: Procurement of compliant components for automotive, food, and general manufacturing sectors. Feature: Product lineage in the SACE Tmax XT family with Ekip LS/I release. Business Impact: Facilitates spare parts compatibility, service support, and consistent performance across the grid. Application: Panel builders and OEMs who standardize on ABB protection products.

Get a Quick Quote for a ABB 2TFH102013R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH102013R1001? Enquire Now

FAQs

XT2H160 uses Withdrawable Circuit-Breakers terminals, enabling safer, rapid maintenance. Ensure proper panel clearance, secure mounting in compatible enclosures, and torque settings per the installation instructions XT2. Plan for the 90 mm wide, 130 mm high, 82.5 mm depth footprint and the 3.32 kg weight to optimize space and handling during retrofits.
The unit is rated for 10 A nominal current and 690 V AC operational voltage, with Icu up to 100 kA at 220–240 V and 70–65 kA at higher voltages. The Ics values vary by voltage: 100 kA at 220–240 V, down to 15 kA at 690 V. This makes it suitable for diverse feeders and motor circuits with high fault currents.
Yes. The XT2H160 adheres to IEC 60947-2 and provides a CE Declaration of Conformity for Tmax XT products. It carries RoHS and REACH declarations, aligning with EU regulatory requirements and enabling compliant procurement for automotive, industrial, and process environments.
Electrical durability is rated at 8000 cycles (120 cycles/hour) and mechanical durability at 25000 cycles (240 cycles/hour). This indicates strong reliability in frequent switching applications, reducing maintenance frequency. Plan for periodic inspection of trip units, wiring integrity, and lever/withdrawable mechanism wear to maximize uptime and minimize unplanned shutdowns.
Ideal for low-voltage distribution in industrial automation, packaging lines, and process control where compact size, high fault protection, and easy maintenance matter. Suitable for 3P feeders, motor control centers, and retrofit projects, especially where compliance with IEC 60947-2, RoHS/REACH, and CE is required to meet safety and regulatory standards.