ABB 2TFH102017R1001 Automatic Circuit Breaker - 690 V/100 kA

Part Number: 2TFH102017R1001
Manufacturer
ABB
Part number
2TFH102017R1001

Quick Summary

ABB XT2H160 Ekip LS/I circuit breaker protects low-voltage distribution and motor circuits in industrial plants. Engineers often struggle to balance reliable protection with minimizing nuisance trips and downtime. This device carries CE conformity via the EC Declaration of Conformity and complies with IEC60947-2, RoHS, and REACH requirements, supporting robust regulatory alignment. For panel builders and OEMs, its 3P design, withdrawable terminals, and 160 A rating translate to safer maintenance, easier upgrades, and improved uptime, while the 100 kA short-circuit rating provides strong fault withstand capability in demanding environments. In short, it couples rigorous protection with practical installability and lifecycle efficiency in SACE Tmax XT applications.

Product Information

Extended Description

2TFH102017R1001 ABB: XT2H160 Ekip LS/I R160 WMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.32 kg
Package Level 1 Width
287 mm
Package Level 1 Height
230 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Gross Weight
3.42 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 13.4 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LS/I
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → 3P, 160 A current rating provides targeted protection for mid-size switchgear and motor feeders. Business Impact → Reduces the risk of equipment damage and unplanned downtime, enabling safer, more predictable production lines. Application → Suitable for LV distribution panels in manufacturing facilities that require reliable motor protection and easy panel integration. Feature → 100 kA short-circuit breaking capacity (Ics/Icu) across applicable voltages ensures robust fault isolation. Business Impact → Enhances safety margins and helps prevent cascading outages, lowering risk for critical processes. Application → Ideal for moderate to high fault scenarios in 690 V AC networks. Feature → Withdrawable circuit-breaker design with standard terminal connections simplifies installation and testing. Business Impact → Decreases commissioning time and maintenance labor, boosting overall installation quality. Application → Used by panel shops and OEMs to accelerate build cycles. Feature → Power loss of 13.4 W per pole at rated conditions improves thermal management and energy efficiency. Business Impact → Reduces heat buildup and cooling requirements in panels, lowering operating costs. Application → Beneficial for dense switchgear where thermal performance matters. Feature → Compliance stack including IEC60947-2, CE DoC, RoHS/REACH, and CMRT support. Business Impact → Eases regulatory auditing and supplier sustainability programs. Application → Critical for global deployments with strict procurement standards. Feature → Compact footprint (90 mm width, 130 mm height, 82.5 mm depth) with 3P configuration. Business Impact → Maximizes panel real estate and simplifies enclosure design. Application → Useful for compact LV installations and modular switchgear. Feature → 3P 690 V AC rated operation with 160 A nominal current. Business Impact → Delivers reliable protection for medium-load circuits while maintaining compatibility with common industrial power architectures. Application → Widely applicable in machine rooms, process lines, and distribution panels.

Get a Quick Quote for a ABB 2TFH102017R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH102017R1001? Enquire Now

FAQs