ABB 2TFH102023R1001 Moulded Case Breaker - XT2 IEC60947-2
Part Number: 2TFH102023R1001
Quick Summary
ABB 2TFH102023R1001 Moulded Case Breaker provides fault protection for industrial power distribution. Operators often face nuisance trips and downtime from undersized protection or poor coordination. It carries CE conformity and IEC60947-2 standards, RoHS compliance, and CMRT reporting, with DoC available. Configured for 3P 160 A operation at up to 690 V AC, it integrates with ABB SACE Tmax XT and Ekip LSI for fast installation and reliable protection. For projects seeking safer, compliant electrical systems, this device delivers long-term reliability while supporting maintenance efficiency and risk reduction.
Product Information
Extended Description
2TFH102023R1001 ABB: XT2H160 Ekip LSI R160 WMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.32 kg
Package Level 1 Width
287 mm
Package Level 1 Height
230 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Gross Weight
3.42 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 13.4 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSI
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Three-pole design with a 160 A rating provides robust protection for three-phase loads. Business Impact: Reduces the risk of line-to-load faults propagating across feeders, improving overall panel reliability. Application: Ideal for motor drives, conveyors, and machine control panels in manufacturing environments. Feature: Rated operational voltage of 690 V AC and insulation up to 1000 V ensures compatibility with industrial distribution networks. Business Impact: Enables safe operation across common European and global low-voltage architectures, lowering integration risk. Application: Suitable for distribution boards and switchgear assemblies in process industries. Feature: Ekip LSI release and XT2 sub-type support fast, selective tripping with reliable coordination. Business Impact: Improves system selectivity, minimizes unnecessary outages, and simplifies maintenance planning. Application: Critical in automated lines and packaging machinery. Feature: High short-circuit breaking capacity at relevant voltages (Ics up to 100 kA at low voltages; Icu up to 100 kA, with 690 V version achieving 15 kA). Business Impact: Protects downstream equipment from severe faults while preserving upstream assets. Application: Power centers and control panels for heavy machinery. Feature: RoHS, REACH declarations, and CMRT reporting demonstrate material compliance. Business Impact: Facilitates regulatory approvals and supply-chain traceability. Application: Projects with strict sustainability and vendor prerequisites. Feature: Withdrawable terminal connection type enhances serviceability. Business Impact: Speeds maintenance, reduces downtime, and improves safety during inline testing. Application: ABB SACE XT maintenance racks and modular switchgear installations.
Get a Quick Quote for a ABB 2TFH102023R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH102023R1001?
Enquire Now
FAQs
This unit uses withdrawable circuit-breaker mounting, making installation straightforward in Tmax XT racks. Verify panel throat width and busbar spacing, connect three phases to the appropriate terminals with the recommended torque, and ensure the Ekip LSI release is correctly configured for your protection scheme. Always follow ABB installation instructions and perform a functional test after wiring to confirm correct trip, reset, and alignment.
Key specs include rated current 160 A, rated operational voltage 690 V AC, rated insulation voltage 1000 V, and rated impulse withstand voltage 8 kV. Short-circuit ratings vary by voltage: Ics up to 100 kA at lower voltages, and Icu up to 100 kA, with the 690 V version typically around 15 kA. Power loss is 13.4 W per pole, with 8000 electrical and 25000 mechanical durability cycles.
Yes. It carries CE conformity and meets IEC60947-2 standards, with RoHS compliance and CMRT reporting. A Declaration of Conformity is available, and material declarations confirm restricted substances compliance. This helps you meet regulatory requirements, support green procurement goals, and simplify supplier audits for European and global projects.
The XT2 160 A MCB suits industrial power distribution in manufacturing lines, conveyors, machine control panels, and processing equipment. Its three-pole design enables balanced protection for three-phase loads, while the withdrawable feature aids maintenance and swap-outs without live-line exposure. It’s compatible with the SACE Tmax XT family and Ekip LSI releases for scalable protection in growing facilities.
Expect reduced downtime due to reliable fault interruption and improved maintenance efficiency from the withdrawable design. Durability figures (8000 electrical cycles, 25000 mechanical cycles) translate to longer service intervals, while a compact footprint and manageable power loss (13.4 W per pole) contribute to energy management and lower lifecycle costs in typical industrial installations.