ABB 2TFH102027R1001 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 2TFH102027R1001
Manufacturer
ABB
Part number
2TFH102027R1001

Quick Summary

ABB 2TFH102027R1001 is a 3-pole moulded case circuit breaker for protecting low-voltage distribution panels. In practice, engineers face nuisance trips and unpredictable downtime when protection isn’t matched to system demand; this device helps reduce that risk with precise tripping characteristics and robust durability. It complies with IEC 60947-2 and carries CE conformity, RoHS compliance, and CMRT alignment to support responsible sourcing. By leveraging the SACE Tmax XT lineage, it also delivers seamless integration with ABB and third‑party panels, delivering faster installation, consistent protection, and measurable uptime improvements for industrial facilities.

Product Information

Extended Description

2TFH102027R1001 ABB: XT2H160 Ekip LSIG R63 WMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.32 kg
Package Level 1 Width
287 mm
Package Level 1 Height
230 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Gross Weight
3.42 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 2.1 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSIG
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P XT2 design with rated current of 63 A and rated operational voltage of 690 V AC. Business Impact: Protects motor feeders and distribution boards with reliable tripping response, reducing fault impact and improving overall plant safety. Application: Suitable for control panels and low-voltage switchgear in manufacturing environments. Feature: High short-circuit capability with Ics up to 100 kA depending on voltage. Business Impact: Provides robust protection against high fault currents, minimizing equipment damage and downtime during faults. Application: Appropriate for critical electrical feeders in process lines and heavy-duty machines.Feature: IEC 60947-2 compliant with CE declaration and RoHS/CMRT alignment. Business Impact: Ensures regulatory compliance, simplifies procurement audits, and supports sustainable sourcing—reducing compliance risk for panel builders. Application: Used in regulated industrial installations and panels requiring standard-compliant protective devices.Feature: Withdrawable/compact 3P design with moderate weight (3.32 kg) and a power loss of 2.1 W per pole. Business Impact: Eases installation and thermal management in crowded switchgear bays, lowering thermal stress and energy use. Application: Ideal for space-constrained panels and modular switchgear configurations.Feature: Release and series compatibility with Ekip LSIG and SACE Tmax XT family. Business Impact: Speeds commissioning and maintenance with familiar ABB ecosystem, reducing engineering time and spare part diversity. Application: Best for multi-vendor or ABB‑centric panel assemblies in plants with frequent upgrades.

Get a Quick Quote for a ABB 2TFH102027R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH102027R1001? Enquire Now

FAQs

This three-pole MCCB is ideal for protection in control panels, distribution boards, and motor feeders within industrial facilities. Its 63 A rating and 690 V AC operating voltage make it a versatile choice for panel builders seeking reliable short-circuit protection and predictable tripping behavior in medium-power applications.
Ics is up to 100 kA for voltages around 220–240 V, trending down for higher voltages (e.g., 70 kA at 380–440 V, 50 kA at 500 V, 30 kA at 525 V, and 15 kA at 690 V). Icu values mirror these ranges, providing robust protection across the voltage spectrum used in industrial mains.
Yes. The device carries CE conformity under EC declarations and adheres to RoHS requirements, with CMRT coverage for responsible sourcing. These certifications simplify regulatory compliance for panel builders and end users in regulated markets.
The unit features a withdrawable 3P design within the SACE Tmax XT family, offering straightforward integration with ABB and third‑party panels. Its compact weight of 3.32 kg and 2.1 W per pole power loss support easier installation, better thermal management, and faster replacement in maintenance cycles.
With a high short-circuit rating, long electrical/mechanical durability (up to 8,000 electrical cycles and 25,000 mechanical cycles), and standardized documentation, this MCCB reduces unplanned outages and simplifies service planning. The compatibility with Ekip LSIG and Tmax XT ecosystems also minimizes spare-part fragmentation and speeds diagnostics.