ABB 2TFH102046R1001 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 2TFH102046R1001
Quick Summary
The 2TFH102046R1001 moulded case circuit breaker provides reliable protection for 690 V industrial power systems. Engineers often grapple with panel downtime and difficult maintenance when selecting protective devices, but this unit’s withdrawable design and clear diagnostics help minimize outages and complexity. It carries IEC 60947-2 certification, CE conformity with a Declaration of Conformity, and RoHS/REACH declarations to support regulatory compliance across global plants. With the SACE Tmax XT lineage and a 63 A rating, this breaker delivers predictable lifecycle costs and scalable protection for power distribution in manufacturing and process environments. In short, it combines robust performance with practical installation and maintenance advantages for modern electrical rooms.
Product Information
Extended Description
2TFH102046R1001 ABB: XT2H160 Ekip I R63 WMP 4P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
4.04 kg
Package Level 1 Width
287 mm
Package Level 1 Height
230 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Gross Weight
4.04 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2.1 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip I
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole XT2 Moulded Case Circuit Breaker design aligns with the SACE Tmax XT family. Business Impact: Enables coordinated protection across multi-phase circuits, reducing fault propagation and improving panel reliability. Application: Suitable for 4P main protection in machine rooms and distribution panels. The XT2 platform’s modular approach supports quick replacement and simplified stock management, improving uptime in high-demand facilities.Feature: 63 amperes rated current with 690 V AC operational voltage. Business Impact: Delivers adequate headroom for motor starter circuits and heavy loads while preserving conductor sizing and energy efficiency. Application: Industrial control panels and process lines requiring consistent current handling without oversizing components.Feature: High fault current withstand: Ics up to 100 kA and Icu up to 100 kA depending on voltage. Business Impact: Provides strong short-circuit resilience, reducing downtime and protecting downstream equipment during faults. Application: Critical in panels feeding large motors, pumps, and presses with high surge potential.Feature: Release Ekip I with EL type and 4P withdrawable configuration. Business Impact: Facilitates fast, safe maintenance and testing without extensive panel downtime. Application: OEM and panel builder environments where rapid core component swaps are routine.Feature: Electrical and mechanical durability specs: 8000 electrical cycles and 25000 mechanical cycles. Business Impact: Extends lifecycle and reduces maintenance intervals and spare-part costs. Application: Continuous production lines where protective devices endure frequent operation.Feature: Compliance and environmental declarations: REACH, RoHS, CMRT, and WEEE considerations. Business Impact: Eases regulatory reporting and supports sustainable procurement strategies. Application: Global manufacturing sites that require traceable, compliant components in warranty and after-sales support.Feature: Data sheet and documentation integration: CE Declaration, Installation Instructions XT2, and extensive technical characteristics. Business Impact: Simplifies engineering validation and commissioning with clear references. Application: Design-phase reviews, panel installation, and maintenance planning with accessible technical data.
Get a Quick Quote for a ABB 2TFH102046R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH102046R1001?
Enquire Now
FAQs
This unit uses a withdrawable 4P configuration suitable for 690 V systems. Plan for proper panel space, busbar access, and clear labeling. Ensure terminal connections are tightened to spec and that the device aligns with the IEC 60947-2 mounting criteria. The design supports quick practical maintenance without extended downtime.
Rated current is 63 A with a rated operational voltage of 690 V AC. It withstands impulse voltages up to 8 kV and provides short-circuit breaking capacities up to 100 kA depending on voltage. The device is designed for AC current with four poles and a release type of EL (Ekip I) for reliable protection.
Yes. The product is listed under IEC 60947-2 and carries CE conformity with Declaration of Conformity. RoHS status and REACH compliance are documented, and CMRT reporting is available, supporting regulatory compliance across global facilities and sustainable procurement practices.
Ideal for low-voltage distribution panels and machine-control circuits in industrial environments. Its 4P design suits multi-phase protection, while the XT family offers scalable protection for motor feeders and power distribution cabinets, enabling reliable protection in manufacturing lines with high fault-current potential.
Electrical durability is rated at 8000 cycles and up to 120 cycles per hour, while mechanical durability reaches 25000 cycles at 240 cycles per hour. The withdrawable design simplifies maintenance, reduces downtime, and supports easier diagnostics. Plan for periodic inspection, torque checks on terminals, and stock of common wear parts aligned with service intervals.