ABB 2TFN000065A1001 XT2L MCCB - IEC60947-2 Compliant
Part Number: 2TFN000065A1001
Quick Summary
ABB XT2L MCCB is a high-performance molded case circuit breaker designed for panel-control and motor protection in industrial electrical systems. Many engineers struggle to balance reliable short-circuit protection with compact size, quick installation, and minimal downtime in harsh plant environments. This device complies with IEC60947-2 and CE declarations, with RoHS compliance and DoC documentation to support regulatory audits. The XT2L leverages ABB EcoSolutions for sustainable end-of-life handling, helping minimize lifetime costs while maintaining reliable overload and short-circuit protection. Designed for 3P systems at 690 V AC with 160 A rated current, it supports easy front-terminal wiring and straightforward field installation. Together with verified Ics and Icu figures and 8 kV impulse rating, the solution offers predictable protection in demanding electrical environments.
Product Information
Extended Description
2TFN000065A1001 ABB: XT2L 160 Ekip Dip LIG In=160A 3p F F
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Width
150 mm
Package Level 1 Height
214 mm
Package Level 1 Depth / Length
130 mm
Package Level 1 Gross Weight
1.3 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 10.8 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
IEC60947-2 compliance, CE declarations, and RoHS status are built into the XT2L design, simplifying regulatory readiness and supplier qualification. This reduces compliance risk and accelerates procurement for control panels and machine rooms. In practical terms, it supports OEMs and integrators needing proven, standards-aligned protection in new builds or retrofits. Feature: 160 A rated current, 3P, 690 V AC with Ics up to 18 kA and Ui of 1000 V. Business impact: robust short-circuit protection and safe fault clearance across motor feeders and drives, enabling better uptime and selectivity. Application: machine drives, conveyors, pumps, and process lines in manufacturing environments. Feature: Front-terminal connection with compact footprint (90.0 mm wide, 130 mm high, 82.5 mm deep) and weight 1.2 kg. Business impact: easier wiring, faster commissioning, and space savings in tight control cabinets. Application: panel assemblies where installation speed and serviceability matter. Feature: Ekip Dip LIG release (Version F) with comprehensive manuals and lifecycle data. Business impact: flexible protection settings and quick adaptation to changing line configurations. Application: modular automation panels and retrofit projects requiring adjustable protection schemes. Feature: ABB EcoSolutions, EPD for Tmax XT, and 55.7% recyclability per EN45555. Business impact: supports sustainability reporting and compliant end-of-life handling while reducing total cost of ownership. Application: procurement strategies targeting environmental and regulatory targets in process industries.
Get a Quick Quote for a ABB 2TFN000065A1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFN000065A1001?
Enquire Now
FAQs
To install the ABB XT2L 160 A MCCB with front-terminal connection, mount the unit securely in a panel, ensuring correct orientation for line and load sides. Connect conductors to the front terminals per the installation instructions, tighten to the specified torque, and verify proper insulation and labeling. Use the Ekip Dip LIG release variants per the manual for configuration and testing in commission-ready panels.
Key electrical ratings for the 160 A XT2L MCCB include three-phase operation at 690 V AC, rated current 160 A, and a 8 kV impulse withstand voltage. It provides a rated service short-circuit breaking capacity up to 18 kA at 690 V and a rated insulation voltage of 1000 V, with RoHS and IEC60947-2 compliance. These ratings support reliable motor protection, selective coordination, and predictable tripping behavior in demanding industrial drives.
Yes. The XT2L 160 A MCCB is designed for motor protection in three-phase drives, offering 3P configuration, robust short-circuit protection (Ics up to 18 kA at 690 V), and a front-terminal wiring option for straightforward installation. The Ekip Dip LIG release provides adjustable protection settings, enabling safe operation of motors, conveyors, and machine tools in manufacturing environments.
The ABB XT2L 160 A MCCB complies with IEC60947-2 and GB/T 14028.2, and includes CE declarations of conformity and RoHS compliance. Documentation also covers DoC and installation guidelines, ensuring regulatory alignment and facilitating audits, traceability, and compliant procurement for global manufacturing and processing facilities.
Lifecycle data include an Environmental Product Declaration (EPD) for Tmax XT XT2 ELT, a recyclability rate of 55.7% per EN45555, and end-of-life disassembly instructions. Packaging disposal guidance and WEEE categorization are provided, along with CMRT for responsible sourcing. This information supports ESG reporting and aligns with corporate targets for circular economy initiatives.