ABB 2TFN000135A1001 Moulded Case Breaker - IEC60947-2
Part Number: 2TFN000135A1001
Quick Summary
ABB 2TFN000135A1001 is a moulded case circuit breaker that protects industrial electrical distributions in demanding environments. Engineers often struggle with downtime due to nuisance tripping or difficult commissioning in compact switchgear, and this model is designed to simplify both tasks. It aligns with IEC60947-2 and CE conformity, with RoHS and REACH declarations supporting global regulatory compliance. The XT2 platform, paired with the Ekip Touch LSIG release, delivers precise protection in a compact footprint, enabling faster cabinet integration and safer maintenance. For panel builders and maintenance teams, this MCCB translates into predictable performance, easier upgrade paths, and reduced total cost of ownership over the equipment lifecycle.
Product Information
Extended Description
2TFN000135A1001 ABB: XT2H 160 Ekip Touch LSIG In=63A 3p F F
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Width
150 mm
Package Level 1 Height
214 mm
Package Level 1 Depth / Length
130 mm
Package Level 1 Gross Weight
1.3 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.7 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 3P 690 V AC rated device offers reliable fault protection in high-energy distribution networks, reducing unplanned downtime and safeguarding critical processes in industries such as manufacturing and process automation. In practice, this means fewer arc flash incidents and shorter outage durations during protection events, improving overall plant availability. Application-friendly front terminal connections simplify wiring during panel assembly, cutting installation time and labor costs while maintaining secure, vibration-resistant terminations for harsh environments. Feature → Business Impact → Application: With Ics 100 kA and Icu 100 kA across applicable voltages, the device delivers strong short-circuit protection that limits damage to feeders and downstream equipment, supporting safer start-ups and faster fault isolation in switchgear assemblies. Feature → Business Impact → Application: The Ekip Touch LSIG release provides intuitive trip-unit management and rapid reconfiguration, which accelerates commissioning and reduces operator training needs in automation projects. Feature → Business Impact → Application: The compact physical footprint (90 mm width, 130 mm height, 82.5 mm depth) enables higher panel density and easier retrofits in existing enclosures, delivering space savings and improved thermal management. Feature → Business Impact → Application: Low power loss of approximately 1.7 W per pole contributes to lower heat generation, increasing efficiency in continuous operation and reducing cooling requirements in constrained electrical rooms. Feature → Business Impact → Application: End-of-life data, including disassembly instructions and environmental declarations (EPD and EN45555 recyclability), supports sustainable disposal and easier end-of-life planning for circular economy initiatives. Feature → Business Impact → Application: Compliance with RoHS and REACH declarations, as well as CMRT considerations, helps manufacturers meet supplier and regulatory requirements, avoiding potential penalties and enabling straightforward certifications for global markets.
Get a Quick Quote for a ABB 2TFN000135A1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFN000135A1001?
Enquire Now
FAQs
Plan for front-terminal connections, ensure panel space for a 3P MCCB, and verify clearance for 90 mm width and 130 mm height. Use proper torque on terminals and follow Ekip Touch LSIG guidelines during setup to ensure accurate trip settings and safe operation.
Three-pole, 63 A rated current, rated operational voltage 690 V AC, insulation voltage 1000 V, Ics and Icu up to 100 kA, and a release type Ekip Touch LSIG. Short-circuit ratings vary by voltage, with a strong protection margin for typical industrial loads.
Yes. The device is specified with the Ekip Touch LSIG release, enabling precise trip adjustments, quick commissioning, and straightforward maintenance within Tmax XT family installations.
It adheres to IEC60947-2 with CE conformity, RoHS and REACH declarations, CMRT for conflict minerals, and includes environmental disclosures such as EPD and recyclability data per EN45555.
Benefits include reduced downtime due to reliable protection, faster commissioning with LSIG, improved panel density for space savings, and lower energy costs from reduced heat loss (approx. 1.7 W per pole). End-of-life and regulatory alignment also lower lifecycle risk and maintenance costs.