ABB 2TFN000138A1001 Automatic Circuit Breaker - IEC60947-2
Part Number: 2TFN000138A1001
Quick Summary
ABB 2TFN000138A1001 is an automatic circuit breaker designed to protect 690 V AC distribution panels in industrial settings. Engineers often face trade-offs between compact installation space, fast trip, and long service life—this device aims to balance all three. It carries IEC 60947-2 conformity, CE declaration of conformity, and RoHS compliance, with documented end-of-life disassembly guidance to support sustainable replacement. As part of the SACE Tmax XT family, it features front-terminal wiring, a 4P design, and a 40 A rated current, reducing panel depth and improving installation efficiency.
Product Information
Extended Description
2TFN000138A1001 ABB: XT2H 160 Ekip Touch LSIG In=40A 4p F F
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Width
150 mm
Package Level 1 Height
214 mm
Package Level 1 Depth / Length
130 mm
Package Level 1 Gross Weight
1.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 4P 40 A, 690 V AC rated current and voltage. Business Impact: Provides robust protection for multi-phase distribution with minimal voltage drop and predictable trip behavior. Application: Ideal for 4-pole protection in industrial control panels using SACE Tmax XT line. Long-tail keywords: 4-pole molded case circuit breaker, 40 A MCCB, 690 V protection. Feature: Front terminal connection. Business Impact: Simplifies wiring, speeds up installation, and reduces field wiring errors. Application: Suitable for compact panels with accessible wiring harnesses. Long-tail keywords: front-terminal MCCB, easy wiring MCCB. Feature: 8 kV rated impulse withstand and 100 kA breaking capacity. Business Impact: Ensures high-energy surge protection and strong fault clearance across common low-voltage networks. Application: Critical for heavy industry switchgear and motor control centers. Long-tail keywords: Iimp 8 kV, Ics 100 kA, Icu 100 kA. Feature: Release type Ekip Touch LSIG with EL trip unit. Business Impact: Improves selective coordination and precise tripping for reduced nuisance trips. Application: Process industries requiring reliable protection with user-friendly trip settings. Long-tail keywords: Ekip Touch LSIG, EL release, selective coordination. Feature: Compliance and sustainability data. Business Impact: Supports responsible procurement with RoHS, CE, EPD, and end-of-life guidelines. Application: Corporate sustainability programs and compliant panel builds. Long-tail keywords: RoHS compliance MCCB, EPD Tmax XT, end-of-life disassembly. Feature: Mechanical and environmental durability. Business Impact: Extends service life in harsh environments, lowering maintenance costs. Application: Outdoor or rugged indoor installations. Long-tail keywords: 8000 electrical cycles, 25000 mechanical cycles, RoHS and EN45555 recyclability.
Get a Quick Quote for a ABB 2TFN000138A1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFN000138A1001?
Enquire Now
FAQs
This 4P MCCB uses front-terminal connections and measures 120 mm width x 130 mm height x 82.5 mm depth, with a weight of 1.6 kg. It is designed for SACE Tmax XT installations, allowing straightforward wiring and panel integration. Ensure adequate clearance and secure torque on terminals per installation guidelines to avoid overheating.
Key specs include rated current 40 A, rated operating voltage 690 V AC, rated insulation voltage 1000 V, and rated impulse withstand voltage 8 kV. It provides Ics up to 100 kA and Icu up to 100 kA across listed voltages, with a 4P configuration and EL release type for selective coordination in protective schemes.
Yes, it is designed to be compatible with the SACE Tmax XT family and uses the Ekip Touch LSIG release unit with EL (electro-mechanical) trip characteristics, delivering precise protection and easy parameter adjustment within Tmax XT2-XT4 environments.
The device complies with IEC 60947-2, supports GB/T 14028.2 in relevant regions, and carries CE declarations with RoHS compliance. Environmental data includes EPD for Tmax XT, and end-of-life guidance is provided to assist disassembly and recycling of the unit.
Electrical durability is rated at 8000 cycles (120 cycles/hour) and mechanical durability at 25000 cycles (240 cycles/hour), which translates to lower replacement frequency and downtime. Front-terminal wiring reduces installation time, while RoHS/EPD considerations support sustainable procurement and operating-cost savings.