ABB 2TFN000214A1001 Moulded Case Circuit Breaker - 60947-2

Part Number: 2TFN000214A1001
Manufacturer
ABB
Part number
2TFN000214A1001

Quick Summary

ABB 2TFN000214A1001 is a 3-pole Moulded Case Circuit Breaker protecting distribution panels and motor circuits for industrial automation and panel builders. Engineers face downtime, space constraints, and compliance needs; this compact unit reduces interruptions while delivering reliable protection and easier wiring and commissioning. It carries CE conformity and RoHS compliance with an Environmental Product Declaration, supporting sustainable procurement and regulatory readiness across projects. Designed for ABB EcoSolutions, the XT2 family enables easy installation and safe integration into modern automation architectures. In practice, this model improves protection coordination, minimizes downtime, and supports responsible end-of-life disposal with clear disassembly and recycling guidance.

Product Information

Extended Description

2TFN000214A1001 ABB: XT2H 160 Ekip Touch Measuring LSIG In=40A 3p F F
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Package Level 1 Width
150 mm
Package Level 1 Height
214 mm
Package Level 1 Depth / Length
130 mm
Package Level 1 Gross Weight
1.3 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch Measuring LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The XT2 3P 40 A design delivers precise fault protection with a high Ics/Icu for fast fault clearing, reducing equipment damage and downtime in distribution panels used in manufacturing lines and process automation. This translates to measurable reliability gains and lower maintenance costs in harsh industrial environments where continuity matters. Feature → Business Impact → Application: Ekip Touch Measuring LSIG release enhances trip accuracy and selectable protection, enabling safer machine control and smoother automation sequencing in panel boards and motor starters. This supports tighter coordination in multi-drive architectures and minimizes nuisance trips in high-load startups. Feature → Business Impact → Application: Rated 690 V AC operation with 1000 V insulation allows broad applicability across industrial feeders, panels, and switchgear, simplifying procurement and reducing part diversity. This is ideal for equipment retrofits or new builds where standardization saves time and inventory. Feature → Business Impact → Application: Front terminal connection and compact XT2 form factor streamline installation, reduce wiring faults, and speed commissioning, making it attractive for retrofit projects and space-constrained control cabinets. Feature → Business Impact → Application: Sustainability and compliance data, including RoHS, EPD, and packaging disposal guidance, support responsible procurement, end-of-life planning, and regulatory reporting for large-scale projects in sectors like energy, water, and manufacturing.

Get a Quick Quote for a ABB 2TFN000214A1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFN000214A1001? Enquire Now

FAQs

This model is part of the SACE Tmax XT2 line and uses a front-terminal connection, designed for straightforward mounting in XT2-compliant panels and control cabinets. It supports easy retrofits and new installations with standardized XT2 characteristics, ensuring consistent protection across the cabinet and drive architecture.
Key ratings include In=40 A, Ui=1000 V, Uimp=8 kV, Ics up to 100 kA and Icu up to 100 kA depending on voltage, with a rated operational voltage of 690 V AC. It is suitable for distribution panels, machine control, and automation feeders where high short-circuit protection and reliable operation are critical.
Yes. The device carries CE conformity documentation and RoHS declarations. It also provides an Environmental Product Declaration (EPD) for Life Cycle considerations, along with waste/disposal guidance aligned with ABB EcoSolutions goals.
With front-terminal connections and a compact XT2 form factor, it simplifies wiring and space planning in existing switchgear. Consider compatible panel cut-outs, torque specs for terminals, and coordination with Ekip Touch LSIG releases to ensure selective tripping in motor and feeder circuits.
Electrical durability is rated at up to 8000 cycles and mechanical durability up to 25000 cycles, supporting long service life in demanding environments. Routine checks should include terminal torque verification and trip unit calibration per the XT2 data sheets; this reduces unplanned downtime and extends asset life.