ABB 2TFN000221A1001 Moulded Case Circuit Breaker - 8 kV

Part Number: 2TFN000221A1001
Manufacturer
ABB
Part number
2TFN000221A1001

Quick Summary

ABB 2TFN000221A1001 is a 4-pole molded-case circuit breaker protecting industrial power distribution. In demanding environments, engineers need reliable protection that minimizes nuisance trips and simplifies maintenance. It complies with IEC60947-2 and GB/T 14028.2, carries CE conformity and a Declaration of Conformity, and provides explicit end-of-life disassembly guidance. Backed by Ekip Touch Measuring LSIG and robust environmental data, this device supports sustainability targets while delivering predictable protection. Designed for efficiency, it integrates with ABB EcoSolutions and the SACE Tmax XT family to streamline panel design, procurement, and lifecycle management in modern manufacturing facilities.

Product Information

Extended Description

2TFN000221A1001 ABB: XT2H 160 Ekip Touch Measuring LSIG In=160A 4p F F
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Package Level 1 Width
150 mm
Package Level 1 Height
214 mm
Package Level 1 Depth / Length
130 mm
Package Level 1 Gross Weight
1.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 10.8 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch Measuring LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 4P, 160 A rated current with front-terminal connections enables quick, clean wiring in control panels, reducing installation time and the risk of wiring errors for industrial automation applications. This translates to measurable downtime reduction and cost savings during commissioning in process industries. Feature → Business Impact → Application: Ekip Touch Measuring LSIG release provides precise, adjustable trip units for targeted coordination, improving safety and uptime across packaging, food and beverage, and metals sectors. Feature → Business Impact → Application: High Ics/Icu ratings across voltages (up to 100 kA at low voltages and up to 15 kA at 690 V) ensure superior fault-handling performance in data centers, OEM machinery, and heavy manufacturing lines. Feature → Business Impact → Application: IEC60947-2 and GB/T 14028.2 compliance, CE declaration, and DoC simplify regulatory audits and supplier qualification for global OEMs. Feature → Business Impact → Application: Environmental and recyclability data (EPD, EN45555) support sustainability reporting, packaging waste reduction programs, and end-of-life planning in lean manufacturing. Feature → Business Impact → Application: Front-accessible dimensions (120 x 130 x 82.5 mm) and 1.6 kg weight enable straightforward retrofit and modular panel upgrades without major enclosure changes.

Get a Quick Quote for a ABB 2TFN000221A1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFN000221A1001? Enquire Now

FAQs

For front-terminal 4P installation, ensure adequate clearance for wiring, secure mounting within the panel, and proper torque on terminal screws as specified in the XT2 installation instructions. The unit weighs 1.6 kg and measures 120 mm wide by 130 mm high with 82.5 mm depth, supporting compact panel layouts in automation and distribution applications.
Rated Service Short-Circuit Breaking Capacity (Ics) is 100 kA at 220–240 VAC, 70 kA at 380–440 VAC, 50 kA at 500 VAC, 30 kA at 525 VAC, and 15 kA at 690 VAC. Rated Ultimate Short-Circuit Breaking Capacity (Icu) follows similar voltage tiers. These values enable protection against high fault currents in diverse industrial networks.
This model is specified for AC use with Rated Operational Voltage 690 V AC and Rated Insulation Voltage 1000 V. It is not intended for direct DC applications. For DC systems, select a suitable DC-rated Tmax XT variant and follow the corresponding installation and safety guidelines.
The device complies with IEC 60947-2 and GB/T 14028.2, includes the CE Declaration of Conformity, and provides installation and maintenance documentation. Additional environmental and supply-chain declarations include REACH, RoHS, CMRT, and End-of-Life disassembly instructions for responsible lifecycle management.
Ekip Touch Measuring LSIG enables precise trip settings and monitoring, reducing nuisance trips and optimizing protection coordination. Electrical durability is rated at 8000 cycles (120 cycles/hour) and mechanical durability at 25000 cycles (240 cycles/hour), supporting longer service life. With End-of-Life disassembly guidance and EPD data, you gain clearer longevity planning and easier regulatory reporting.