ABB 2TFN000259A1001 Moulded Case Circuit Breaker - 60947-2
Part Number: 2TFN000259A1001
Quick Summary
ABB 2TFN000259A1001 Moulded Case Circuit Breaker is a reliable protection device for industrial power panels and motor feeders. Engineers often face space constraints, long downtimes, and coordination challenges when upgrading legacy protection systems. This unit complies with IEC 60947-2 and CE declarations, and ABB offers UL 2799 Zero Waste To Landfill validation and an End-of-Life disassembly guide. In practice, it delivers compact installation, front-terminal access, and robust trip performance, supporting safer, more efficient plants while aligning with modern sustainability goals.
Product Information
Extended Description
2TFN000259A1001 ABB: C.BREAKER TMAX XT2H160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP Hi-Touch LSI R 63 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Product Environmental Information Tmax XT
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 1.70 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Hi-Touch LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
The four-pole design with fixed terminals delivers precise current interruption for 63 A at up to 690 V AC, reducing fault propagation and equipment damage with reliable Ics up to 100 kA. The Ekip Hi-Touch LSI release enables fast, coordinated trips, improving plant safety and uptime in motor feeder circuits. With 8000 electrical and 25000 mechanical durability cycles, maintenance cycles are extended and total cost of ownership is lowered for high-demand panels. Environmental compliance, RoHS/REACH, EPD data, and 55.7% recyclability support sustainability targets and regulatory readiness. Front-terminal installation and compatibility with the SACE Tmax XT2 family simplify panel design and harnessing, while a low power loss of 1.70 W per pole helps reduce heat and cooling requirements. The product’s lifecycle data and DoC enable easy audits and robust change management.
Get a Quick Quote for a ABB 2TFN000259A1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFN000259A1001?
Enquire Now
FAQs
Install as a fixed, four-pole MCCB with front-terminal connections for rapid wiring. Confirm compatible panel design by checking the SACE Tmax XT2 family interfaces, then wire per the installation instructions. The Ekip Hi-Touch LSI release offers on-site adjustments to achieve selective tripping without sacrificing protection, ensuring safe and compliant panel operation.
For 690 V AC, the Rated Service Short-Circuit Breaking Capacity (Ics) is 15 kA, while the Rated Ultimate Short-Circuit Breaking Capacity (Icu) remains 70 kA across several higher voltages. This enables robust protection for equipment and motors in demanding industrial networks without nuisance tripping during transient faults.
Yes, the XT2 subtype is designed to be compatible with the Tmax XT2 family. It uses the EL release type in conjunction with Ekip Hi-Touch LSI, delivering precise, rapid trips and easy field adjustments to match system coordination and protection settings.
This product is certified under IEC 60947-2 with CE Declaration of Conformity. It also supports environmental programs like RoHS and REACH, offers an Environmental Product Declaration (EPD) for Tmax XT XT2 ELT, and provides end-of-life documentation including disassembly guides and waste-to-landfill validation programs.
Electrical durability is rated at 8000 cycles (120 cycles/hour) and mechanical durability at 25000 cycles (240 cycles/hour), reducing maintenance frequency. With 1.70 W power loss per pole and front-terminal installation, heat generation is minimized and servicing is simplified, driving lower total cost of ownership in high-demand facilities.