ABB 2TFN000298A1001 Moulded Case Breaker - IEC 60947-2
Part Number: 2TFN000298A1001
Quick Summary
ABB 2TFN000298A1001 Moulded Case Circuit Breaker provides reliable overcurrent protection for low and mid-voltage installations in industrial power distribution systems. Many teams struggle with safe, consistent operation during startup and rapid fault isolation in densely wired panels. This device carries IEC 60947-2 compliance and CE conformity, backed by RoHS and REACH declarations, ensuring regulatory alignment across markets. The front-terminal XT2 design with Ekip Hi-Touch LSIG release delivers precise, fast tripping and simple maintenance, reducing downtime. For asset owners, the combination of compact form factor, robust 40 A rating, and 8 kV impulse withstand supports efficient panel design and cost control while enabling sustainable, compliant electrical protection.
Product Information
Extended Description
2TFN000298A1001 ABB: C.BREAKER TMAX XT2H160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP Hi-Touch LSIG R 40 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Product Environmental Information Tmax XT
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Hi-Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4 | Operation and maintenance manual for Ekip Touch Trip Units for SACE Tmax XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Four-pole fixed configuration with front terminals. Business Impact → Simplifies wiring, reduces panel depth, and speeds installation and maintenance by providing secure, easily accessible connections. Application → Ideal for control panels in manufacturing lines and process equipment where compact, reliable protection is essential. Feature → 40 A rated current with 690 V operating range. Business Impact → Delivers precise protection for common machine loads while avoiding nuisance trips, increasing line uptime. Application → Motor control centers, distribution boards, and feeder circuits in packaging and food & beverage facilities. Feature → High short-circuit ratings across voltages (Ics up to 100 kA at low voltages; Icu up to 70–100 kA depending on voltage). Business Impact → Maintains circuit integrity during faults and protects downstream equipment, reducing collateral damage. Application → Critical equipment in heavy machinery, conveyors, and automated lines. Feature → Ekip Hi-Touch LSIG release with EL trip type. Business Impact → Delivers precise tripping and straightforward testing with front-access maintenance, cutting service time. Application → Field upgrades, OEM panels, and retrofits where quick, safe operation is required. Feature → Environmental compliance and sustainable design (EPD, RoHS, REACH, 55.7% recyclability). Business Impact → Supports regulatory requirements and lifecycle responsibility, lowering end-of-life costs. Application → Projects with sustainability targets, public sector specs, and companies pursuing green procurement. Feature → ABB EcoSolutions endorsement and UL 2799 Zero Waste To Landfill validation option. Business Impact → Demonstrates strong environmental stewardship and market appeal in waste reduction initiatives. Application → Global tenders and long-term capital projects where sustainability and compliance drive procurement decisions. Feature → Compact form factor: 120 mm width, 130 mm height, 82.5 mm depth; weight 1.6 kg. Business Impact → Enables tight cabinet layouts and easier thermal management by allowing better spacing and ventilation planning. Application → Space-constrained switchgear and panel assemblies in automation plants.
Get a Quick Quote for a ABB 2TFN000298A1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFN000298A1001?
Enquire Now
FAQs
The device is a four-pole fixed circuit breaker with front terminals, designed for standard low-voltage switchgear. It simplifies wiring, reduces panel depth, and speeds assembly, making it an ideal choice for space-constrained control panels in manufacturing and process environments.
Key ratings include 40 A rated current, Ue up to 690 V AC / 500 V DC, Ui 1000 V, 8 kV rated impulse withstand, and IEC 60947-2 compliance. Ics and Icu vary with voltage, reaching up to 100 kA at lower voltages and up to 70–100 kA at higher voltages, depending on configuration.
The unit aligns with RoHS and REACH declarations, CE conformity, and EPD coverage for Tmax XT/XT2. It also supports ABB EcoSolutions and can be part of Zero Waste To Landfill validation programs, helping meet sustainability and regulatory requirements across markets.
Ekip Hi-Touch LSIG provides a precise, fast-acting release with EL trip logic, while offering front-access testing and maintenance. This reduces service time, improves fault diagnostics, and simplifies routine panel checks in industrial environments.
Refer to IEC 60947-2 for low-voltage molded-case circuit breakers, GB/T 14028.2 as applicable, the CE Declaration of Conformity, installation instructions, and the SACE Tmax XT technical catalog for specific characteristics and wiring requirements.