ABB BC6-40-00-07 Mini Contactor - UL/CSA Certified

Part Number: GJL1213201R0007
Manufacturer
ABB
Part number
GJL1213201R0007

Quick Summary

ABB BC6-40-00-07 Mini Contactor reliably controls single- and three-phase loads in industrial, commercial, and residential equipment. In crowded control panels, space-saving design and quiet operation reduce installation time and service downtime. It carries CE markings and UL/CSA listings, with CB and CCC declarations, and an IP20 protection rating for safe indoor use. The product aligns with EN/IEC standards for motor protection and control, ensuring compliance across global projects. With a compact 4-pole design and screw terminals, it delivers dependable performance in demanding environments while fitting neatly into DIN rails and on walls, supporting efficient panels and machines and offering predictable lifecycle costs.

Product Information

Extended Description

GJL1213201R0007 ABB: The BC6-40-00 mini contactor is a compact 4 pole contactor with screw terminals. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 4 kW (AC-3) and 20 A (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil, a switch position indication and the integrated possibility for rail or wall mounting.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6
Product Net Width
52.5 mm
Product Net Depth / Length
46.7 mm
Product Net Height
57.5 mm
Product Net Weight
0.175 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1 | IEC 60335-2-40 A2L
Rated Operational Voltage
Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 50 Hz | Main Circuit 60 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 20 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 20 A | (220 / 240 V) 55 °C 16 A | (380 / 440 V) 40 °C 20 A | (380 / 440 V) 55 °C 16 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 9 A | (400 V) 55 °C 9 A | (500 V) 55 °C 6.5 A | (690 V) NO 55°C 3.5 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 2.2 kW | (400 V) Three Phase 4 kW | (500 V) Three Phase 4 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
12 V DC
Coil Consumption
Average Holding Value DC 3.5 W | Average Pull-in Value DC 3.5 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | Flexible 1/2x 1 ... 2.5 mm² | Rigid 1/2x 1 ... 4 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 1 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | Flexible 1/2x 1 ... 2.5 mm² | Rigid 1/2x 1 ... 4 mm²
Wire Stripping Length
Main Circuit 9 mm
Degree of Protection
Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Recommended Screw Driver
M3 | Pozidriv 1
Tightening Torque
Control Circuit 0.8 ... 1.1 N·m | Main Circuit 0.8 ... 1.1 N·m
Terminal Type
Screw Terminals
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(300 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.25 Hp | (200 V AC) Three Phase 1 Hp | (220 ... 240 V AC) Three Phase 2 Hp | (230 V AC) Single Phase 0.5 Hp | (440 ... 480 V AC) Three Phase 3 Hp | (550 ... 600 V AC) Three Phase 1 Hp
Connecting Capacity Main Circuit UL/CSA
Stranded 1/2x 22-10 AWG
Tightening Torque UL/CSA
Control Circuit 7 in·lb | Main Circuit 7 in·lb
Full Load Amps Motor Use
(115 V AC) Single Phase 5.8 A | (200 V AC) Three Phase 4.8 A | (220 ... 240 V AC) Three Phase 6.8 A | (230 V AC) Single Phase 4.9 A | (440 ... 480 V AC) Three Phase 4.8 A | (550 ... 600 V AC) Three Phase 1.7 A
Ambient Air Temperature
Operation -20 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End Of Life Instruction B(C)6, B(C)7, K(C)6, VB(C)6, VB(C)7
Environmental Product Declaration - EPD
Environmental Product Declaration PEP B(C)6, B(C)7 (EN)
A2L Certificate – IEC
A2L Certificate - B6-, B7-, K6- series, CA6, CAF6 - Mini Contactor
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cULus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
Package Level 1 Units
box 10 piece
Package Level 1 Width
115 mm
Package Level 1 Depth / Length
280 mm
Package Level 1 Height
54 mm
Package Level 1 Gross Weight
1.82 kg
Package Level 1 EAN
4013614415340
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
The 4-pole BC6-40-00-07 mini contactor provides four normally open main contacts, enabling compact control of multiple loads from a single device, reducing wiring complexity and panel footprint. Business impact: streamlined wiring, faster commissioning, and reduced cabinet space. Application: machine tools and HVAC systems where space is at a premium. The 12 V DC coil delivers reliable energisation with a low 3.5 W pull-in/holding power, minimizing heat generation and energy use in control circuits. Application: low-power control panels and safety interlocks where energy efficiency matters, improving overall system reliability. Screw terminal connections offer secure, vibration-resistant wiring for adverse environments, supporting flexible conductor sizes and straightforward field maintenance. Application: heavy-duty industrial installations where maintenance windows are tight. DIN rail mounting compatibility (TH35-15/TH35-7.5) and optional wall mounting simplify integration into standard enclosures and retrofit projects, reducing installation time and ensuring consistent alignment with supporting infrastructure. Application: modular automation cabinets and retrofit projects in manufacturing and building automation. IP20 protection on both control and main circuit terminals safeguards against dust ingress and incidental contact, improving safety and easing compliance with installation standards. Application: indoor electrical protection and control in residential, commercial, and light industrial setups. The contactor is rated for AC-3 and AC-1 duty per IEC/UL standards, delivering predictable performance for motor-start and control circuits in variable voltage environments. Application: motor control centers and pump stations with diverse voltage requirements, enabling scalable, future-proof designs.

Get a Quick Quote for a ABB GJL1213201R0007

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB GJL1213201R0007? Enquire Now

FAQs

The BC6-40-00-07 uses a 12 V DC control coil and features 4 main NO contacts with no NC contacts. This configuration supports switching multiple loads from a single device and simplifies wiring in compact control panels.
Yes. The device is designed for DIN rail mounting using TH35-15 or TH35-7.5 rails, and it can also be mounted on a wall. This provides installation flexibility in standard enclosures and retrofit projects.
Rated operational power AC-3 varies by voltage: at 230 V, 55 °C you can achieve about 9 A; at 400 V and 500 V it remains 9 A; at 690 V, it is 3.5 A for the NO configuration. These ratings guide motor and pump starting applications in industrial controls.
The contactor carries CE and UL/CSA listings, along with CB/CCC declarations and related RoHS/REACH compliance. These certifications support global approvals for panel builders and OEMs across multiple regions.
Use screw terminals with appropriate conductor sizes (1/2 x 1 to 2.5 mm² for main, 1/2 x 1 to 2.5 mm² for control), respect tightening torques (0.8–1.1 N·m for both circuits), and follow the dimension and mounting diagrams. The design supports secure, vibration-resistant connections in demanding industrial environments.