ABB GJL1313009R0013 Mini Contactor - IEC/UL Certifications

Part Number: GJL1313009R0013
Manufacturer
ABB
Part number
GJL1313009R0013

Quick Summary

The ABB GJL1313009R0013 Mini Contactor is a compact DC control device for switching 3-phase loads in industrial automation. End users in data centers, buildings, and light industrial lines face tighter footprints and greater maintenance demands, especially in aging panels. This mini contactor delivers reliability with a noiseless coil, soldering-pin terminals for quick PCB mounting, and a rugged 3P configuration ideal for AC-3 and AC-1 duties. CE, UL/CSA, and RoHS compliance, plus IP20 protection, are backed by robust data sheets, DoCs, and industry-standard tests, helping procurement teams validate compliance quickly. In practice, its DIN-rail compatibility and efficient 60 V DC coil deliver measurable business value through faster installation and fewer field failures.

Product Information

Extended Description

GJL1313009R0013 ABB: The BC7-30-01-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil and a switch position indication.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6 (-P)
Product Net Width
47.5 mm
Product Net Depth / Length
47.7 mm
Product Net Height
45.2 mm
Product Net Weight
0.17 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V AC | Auxiliary Circuit 250 V DC | Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 60 Hz | Main Circuit 50 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A | (220 / 240 V) 55 °C 12 A | (380 / 440 V) 40 °C 12 A | (380 / 440 V) 55 °C 12 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 12 A | (400 V) 55 °C 12 A | (500 V) 55 °C 9 A | (690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A | (120 V) 4 A | (500 V) 2 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A | (110 V) 0.7 A | (220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW | (400 V) Three Phase 5.5 kW | (500 V) Three Phase 5.5 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV | Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-15) 600 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-13) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V | Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
60 V DC
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20 | Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(600 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp | (200 V AC) Three Phase 2 Hp | (220 ... 240 V AC) Three Phase 3 Hp | (230 V AC) Single Phase 1.5 Hp | (440 ... 480 V AC) Three Phase 5 Hp | (550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A | (200 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 9.6 A | (230 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 6.1 A
Ambient Air Temperature
Operation -25 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cURus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
UL Certificate
UL Certificate of Compliance - B6, B7 (Pin/Faston) - Mini Contactor
Package Level 1 Units
carton 10 piece
Package Level 1 Width
108 mm
Package Level 1 Depth / Length
247 mm
Package Level 1 Height
69 mm
Package Level 1 Gross Weight
1.775 kg
Package Level 1 EAN
4013614418648
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature → Business Impact → Application: 3-pole design with 3 main NO contacts and 1 NC auxiliary contact enables reliable switching of single- or three-phase loads up to 5.5 kW (AC-3) while providing an auxiliary feedback signal for diagnostics. This translates to smaller panel enclosures and lower wiring complexity in commercial buildings and industrial plants. Feature → The soldering-pin terminals simplify PCB mounting and field repair in OEM equipment or control panels, reducing assembly time and fault risk. Benefit → Faster installation and easier maintenance in space-constrained environments. Application → Ideal for compact control panels in building automation and light industrial machinery. Feature → Noiseless coil delivers quiet operation, improving operator comfort and reducing audible energy consumption in quiet environments. Benefit → Less distraction in control rooms and safer, more reliable operation in customer-facing installations. Application → Data centers, hospitals, and offices with critical HVAC and lighting control. Feature → 60 V DC coil with 0.85–1.1 x Uc operating range offers compatibility with modern DC control architectures. Benefit → Lower power supply requirements and faster relay pull-in in low-voltage control schemes. Application → PLC-based starters and intelligent control panels. Feature → DIN rail mounting options TH35-15 or TH35-7.5 enable fast, modular installation. Benefit → Scalable panel design and straightforward retrofits in existing installations. Application → OEM equipment and switchgear assemblies. Feature → 1.4 W power loss per pole supports energy efficiency in continuous operation. Benefit → Reduced heat and energy costs in dense panel environments. Application → Continuous control in manufacturing lines. Feature → IP20 protection on main, control, and auxiliary terminals improves safety and reliability in indoor installations. Benefit → Safer handling and longer service life in dusty or cluttered environments. Application → Commercial buildings and industrial facilities with accessible terminals.

Get a Quick Quote for a ABB GJL1313009R0013

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB GJL1313009R0013? Enquire Now

FAQs

This device is designed for versatile DIN rail mounting on TH35-15 or TH35-7.5 rails, enabling quick installation in compact control cabinets and OEM panels without additional brackets. The post-assembly stability supports vibration-prone environments typical in industrial automation, while maintaining easy access for maintenance checks.
AC-3 ratings include up to 12 A at 230 V and 400 V, with 5.5 kW achievable at higher voltages (500 V). DC-13 ratings are 2.5 A at 24 V and 0.4 A at 220/240 V. These values support reliable motor control and signaling in multi-voltage systems, with safety margins aligned to IEC/EN 60947 standards.
Yes. The device uses a 60 V DC control circuit and features a coil operating range of 0.85–1.1 x Uc at temperatures up to 55 C. This makes it well suited for modern DC control architectures, enabling compact, energy-efficient switching without large auxiliary power supplies.
The product is CE and UL/CSA approved, with RoHS/REACH compliance and DoCs, plus UKCA and CCC declarations. These certifications support global procurement, simplify regulatory reviews, and help customers meet cross-border regulatory requirements in industrial and building automation projects.
Key ROI factors include 10 million mechanical cycles, 1.4 W per pole power loss, and soldering-pin terminals for quick field mounting or replacement. These features reduce downtime, streamline maintenance, and lower total cost of ownership in high-availability systems.