ABB GJL1313009R0103 Mini Contactor - UL/CE Listed

Part Number: GJL1313009R0103
Manufacturer
ABB
Part number
GJL1313009R0103

Quick Summary

ABB GJL1313009R0103 Mini Contactor is a compact 3-pole switch used to reliably control motors and loads in space-constrained panels. When panel real estate is tight, bulky starters can complicate wiring and extend installation. This device complies with IEC/EN 60947-1, IEC/EN 60947-4-1 and UL 60947-1/4-1, with CE declarations and IP20 protection, delivering confidence across global certifications. Designed for DIN rail mounting TH35-15 or TH35-7.5, it fits neatly into automated panels in residential, commercial, and industrial environments, enabling efficient motor control and streamlined maintenance in real-world workflows.

Product Information

Extended Description

GJL1313009R0103 ABB: The BC7-30-10-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil and a switch position indication.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6 (-P)
Product Net Width
47.5 mm
Product Net Depth / Length
47.7 mm
Product Net Height
45.2 mm
Product Net Weight
0.17 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V AC | Auxiliary Circuit 250 V DC | Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 50 Hz | Main Circuit 60 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A | (220 / 240 V) 55 °C 12 A | (380 / 440 V) 40 °C 12 A | (380 / 440 V) 55 °C 12 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 12 A | (400 V) 55 °C 12 A | (500 V) 55 °C 9 A | (690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A | (120 V) 4 A | (500 V) 2 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A | (110 V) 0.7 A | (220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW | (400 V) Three Phase 5.5 kW | (500 V) Three Phase 5.5 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV | Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-15) 600 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-13) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V | Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
60 V DC
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20 | Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(600 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp | (200 V AC) Three Phase 2 Hp | (220 ... 240 V AC) Three Phase 3 Hp | (230 V AC) Single Phase 1.5 Hp | (440 ... 480 V AC) Three Phase 5 Hp | (550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A | (200 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 9.6 A | (230 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 6.1 A
Ambient Air Temperature
Operation -25 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cURus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
UL Certificate
UL Certificate of Compliance - B6, B7 (Pin/Faston) - Mini Contactor
Package Level 1 Units
carton 10 piece
Package Level 1 Width
108 mm
Package Level 1 Depth / Length
247 mm
Package Level 1 Height
69 mm
Package Level 1 Gross Weight
1.775 kg
Package Level 1 EAN
4013614418709
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature: 60 V DC coil enables direct control of DC-supplied control circuits. Benefit: reduces wiring complexity and improves response times for DC-driven automation in HVAC and small machinery. Application: panel boards and control circuits where DC coil drives are preferred for reliability. Feature: 3 main NO contacts plus 1 auxiliary NO contact. Benefit: expands control options for interlocks and signaling while preserving compact footprint. Application: coordinated motor and signal switching in compact starters. Feature: Soldering pins. Benefit: robust, vibration-resistant connections that simplify in-house wiring and field servicing. Application: retrofit and new installations where soldered terminations deliver long-term reliability. Feature: 47.5 mm width, 47.7 mm depth, 45.2 mm height; 0.17 kg. Benefit: space-saving density that supports dense panel layouts and easier integration into cramped enclosures. Application: DIN-rail mounted control assemblies in commercial buildings and light industry. Feature: IP20 protection and TH35 DIN rail mounting. Benefit: safe, easy installation with proven mechanical durability for everyday industrial environments. Application: factory automation, building services, and control cabinets requiring reliable protection and mounting clarity. Feature: AC-3 ratings up to 12 A, power loss 1.4 W per pole; mechanical durability 10,000,000 cycles. Benefit: energy-efficient operation with reduced heat generation and extended lifecycle, lowering maintenance and replacement costs. Application: motor control at 230–400 V OEM equipment and process lines in manufacturing settings.

Get a Quick Quote for a ABB GJL1313009R0103

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB GJL1313009R0103? Enquire Now

FAQs

It uses a 60 V DC coil and features three main normally-open contacts (3 NO) plus one normally-open auxiliary contact (1 NO), in a 3P arrangement for compact motor control.
Yes. It is designed for TH35-15 (35 × 15 mm) and TH35-7.5 (35 × 7.5 mm) DIN rails, facilitating quick, secure installation in control cabinets.
It complies with IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1, and is CE/UKCA certified, with IP20 protection for control circuitry.
Rated for main circuit voltages up to 690 V and AC-3 operation up to 12 A (230–400 V range typically, with other voltages specified), suitable for motors up to several kilowatts depending on voltage and duty cycle.
Low coil power loss of 1.4 W per pole reduces heat and energy usage, while mechanical durability of 10,000,000 cycles supports long service life and lower maintenance costs in demanding production environments.