ABB BC7-30-01-P-16 Mini Contactor - 3P 48V DC UL/CSA
Part Number: GJL1313009R1016
Quick Summary
ABB BC7-30-01-P-16 mini contactor enables reliable motor control for small to medium loads in building panels. Engineers often face space constraints, noise, and the need for dependable operation in compact control enclosures. This device carries UL/CSA certifications alongside CE marking and RoHS compliance, ensuring safe global deployment. With a 48 V DC coil, soldering-pin terminals, and DIN rail mounting, it simplifies installation, reduces wiring time, and enhances panel density. Designed for residential, commercial, and light industrial applications, it delivers steady switching performance while protecting circuits and extending equipment life.
Product Information
Extended Description
GJL1313009R1016 ABB: The BC7-30-01-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil and a switch position indication.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6 (-P)
Product Net Width
47.5 mm
Product Net Depth / Length
47.7 mm
Product Net Height
45.2 mm
Product Net Weight
0.17 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1 | IEC 60335-2-40 A2L
Rated Operational Voltage
Auxiliary Circuit 690 V AC | Auxiliary Circuit 250 V DC | Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 60 Hz | Main Circuit 50 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A | (220 / 240 V) 55 °C 12 A | (380 / 440 V) 40 °C 12 A | (380 / 440 V) 55 °C 12 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 12 A | (400 V) 55 °C 12 A | (500 V) 55 °C 9 A | (690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A | (120 V) 4 A | (500 V) 2 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A | (110 V) 0.7 A | (220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW | (400 V) Three Phase 5.5 kW | (500 V) Three Phase 5.5 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV | Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-15) 600 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-13) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V | Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
48 V DC
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20 | Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(600 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp | (200 V AC) Three Phase 2 Hp | (220 ... 240 V AC) Three Phase 3 Hp | (230 V AC) Single Phase 1.5 Hp | (440 ... 480 V AC) Three Phase 5 Hp | (550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A | (200 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 9.6 A | (230 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 6.1 A
Ambient Air Temperature
Operation -25 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End Of Life Instruction B(C)6-P, B(C)7-P, K(C)6-P, VB(C)6-P, VB(C)7-P
Environmental Product Declaration - EPD
Environmental Product Declaration PEP B(C)6, B(C)7 (EN)
A2L Certificate – IEC
A2L Certificate - B6-, B7-, K6- series, CA6, CAF6 - Mini Contactor
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cURus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
UL Certificate
UL Certificate of Compliance - B6, B7 (Pin/Faston) - Mini Contactor
Package Level 1 Units
box 10 piece
Package Level 1 Width
108 mm
Package Level 1 Depth / Length
247 mm
Package Level 1 Height
69 mm
Package Level 1 Gross Weight
1.775 kg
Package Level 1 EAN
4013614418747
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
The compact 3-pole design with a single NC auxiliary contact and soldering-pin terminals reduces wiring complexity and saves panel space, enabling denser control circuits and faster assembly. The 48 V DC coil delivers energy-efficient operation and improved coil reliability, minimizing energization losses in control cabinets. DIN rail mounting compatibility (TH35-15 or TH35-7.5) and a compact footprint of approximately 47.5 mm width and 47.7 mm depth simplify retrofit and new installations, ensuring quick, tool-free integration into automation cabinets. Rated AC-3 current up to 12 A at typical industrial voltages allows reliable motor and load switching for up to 5.5 kW, delivering predictable performance with lower total cost of ownership. RoHS, REACH, and various certification attest to regulatory compliance and long-term sustainability, while the 10 million mechanical life cycles provide durability in demanding hourly duty. Versatile mounting on DIN rails and availability of SDS-compatible documentation reduce commissioning risk and support maintenance planning for OEMs and system integrators.
Get a Quick Quote for a ABB GJL1313009R1016
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB GJL1313009R1016?
Enquire Now
FAQs
This mini contactor is designed for DIN rail mounting on TH35-15 or TH35-7.5 rails, enabling quick installation in standard control panels. The compact footprint and soldering-pin terminals also support PCB wiring where preferred, offering flexible integration for OEMs and panel builders.
The device supports AC-3 operation at 230 V with up to 12 A, enabling up to 5.5 kW loads, and the coil operates at 48 V DC with IEC compatible DC control limits. Main circuit voltage up to 690 V AC and 220 V DC are supported, with protection IP20.
Yes. Its three-pole design, 12 A AC-3 rating, and 5.5 kW AC-3 capacity make it suitable for small HVAC fans, pumps, and compressor loads in commercial equipment, while its compact size helps minimize panel footprint without compromising reliability.
UL/CSA certifications ensure compliance with North American electrical safety standards, CE marks indicate conformity with European directives, and RoHS/REACH declarations support environmental and chemical safety. These certifications simplify global deployment and reduce validation time in multi-region projects.
The device offers a mechanical durability of up to 10,000,000 cycles and a low power loss of 1.4 W per pole under rated operation, reducing wear and energy use over time. Regular inspection of solder joints and terminal integrity during PM schedules will help sustain reliability in demanding environments.