ABB GJL1313009R1106 Mini Contactor - 48 V DC, Soldering Pins
Part Number: GJL1313009R1106
Quick Summary
ABB GJL1313009R1106 Mini Contactor controls three‑phase loads in tight panels. This compact 3-pole device includes one NO auxiliary contact and soldering pins, enabling reliable wiring where space is at a premium. It carries critical certifications for global use, including IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1, and CE declarations, supporting compliant installations. Designed for DIN rail mounting with TH35-15 or TH35-7.5 rails, it integrates easily with standard motor protection and control gear. The 48 V DC coil offers low power consumption (3.5 W hold/pull-in) and a compact footprint, translating to reduced panel space and lower lifecycle costs in residential, commercial, and light industrial applications.
Product Information
Extended Description
GJL1313009R1106 ABB: The BC7-30-10-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 12 A (AC-1) or switching of control signals. Further features are the noiseless and hum-free coil and a switch position indication.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6 (-P)
Product Net Width
47.5 mm
Product Net Depth / Length
47.7 mm
Product Net Height
45.2 mm
Product Net Weight
0.17 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1 | IEC 60335-2-40 A2L
Rated Operational Voltage
Auxiliary Circuit 690 V AC | Auxiliary Circuit 250 V DC | Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 60 Hz | Main Circuit 50 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A | (220 / 240 V) 55 °C 12 A | (380 / 440 V) 40 °C 12 A | (380 / 440 V) 55 °C 12 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 12 A | (400 V) 55 °C 12 A | (500 V) 55 °C 9 A | (690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A | (120 V) 4 A | (500 V) 2 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A | (110 V) 0.7 A | (220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW | (400 V) Three Phase 5.5 kW | (500 V) Three Phase 5.5 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV | Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-15) 600 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-13) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V | Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
48 V DC
Coil Consumption
Average Holding Value DC 3.5 W | Average Pull-in Value DC 3.5 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20 | Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Mini Contactor
Product Name
Mini Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(600 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp | (200 V AC) Three Phase 2 Hp | (220 ... 240 V AC) Three Phase 3 Hp | (230 V AC) Single Phase 1.5 Hp | (440 ... 480 V AC) Three Phase 5 Hp | (550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A | (200 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 9.6 A | (230 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 6.1 A
Ambient Air Temperature
Operation -25 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End Of Life Instruction B(C)6-P, B(C)7-P, K(C)6-P, VB(C)6-P, VB(C)7-P
Environmental Product Declaration - EPD
Environmental Product Declaration PEP B(C)6, B(C)7 (EN)
A2L Certificate – IEC
A2L Certificate - B6-, B7-, K6- series, CA6, CAF6 - Mini Contactor
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cURus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
UL Certificate
UL Certificate of Compliance - B6, B7 (Pin/Faston) - Mini Contactor
Package Level 1 Units
box 10 piece
Package Level 1 Width
108 mm
Package Level 1 Depth / Length
247 mm
Package Level 1 Height
69 mm
Package Level 1 Gross Weight
1.775 kg
Package Level 1 EAN
4013614418754
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
Feature: 3-pole with 3 NO main contacts and 1 NO auxiliary contact. Benefit: enables reliable multi-load switching in a single device while maintaining a compact footprint, ideal for small control panels. Application: motor control and equipment starters in compact machines up to 5.5 kW AC-3 ratings. Feature: 48 V DC coil with 3.5 W consumption. Benefit: reduced heat generation and energy use, improving panel efficiency and allowing longer service intervals. Application: control circuits in building automation and industrial automation where energy efficiency matters. Feature: Soldering pin terminals. Benefit: robust, easy-to-wire connections with predictable solder joints; reduces field wiring errors. Application: fast field wiring during installation and servicing. Feature: DIN rail mounting TH35-15 / TH35-7.5. Benefit: quick, standardized mounting on common DIN rails; simplifies retrofits and panel design. Application: modular machine cabinets, control panels, and automation racks. Feature: IP20 protection on main, control, and auxiliary circuits. Benefit: improved reliability in typical indoor environments; reduced risk of incidental contact. Application: standard industrial and commercial environments with moderate dust exposure. Feature: Compact dimensions (47.5 mm × 47.7 mm × 45.2 mm) and 0.17 kg weight. Benefit: minimal panel footprint and lightweight installation in space-constrained enclosures. Application: densely packed control panels in buildings and machinery. Feature: Certifications and RoHS compliance (IEC/EN 60947 family, UL/CSA, CE/UKCA). Benefit: regulatory-aligned product lifecycle, easier cross-border deployments, and sustainability compliance. Application: global installations in commercial and industrial settings.
Get a Quick Quote for a ABB GJL1313009R1106
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB GJL1313009R1106?
Enquire Now
FAQs
The device mounts on TH35-15 or TH35-7.5 DIN rails for quick integration into standard control panels. Wire the 48 V DC coil to the control circuit using proper gauge for compact 0.5 to 2 A control lines; connect the 3 main NO contacts and the 1 auxiliary NO contact for the intended load configuration. Follow the data sheet for correct polarity and safe wiring practices to ensure reliable operation.
For AC-3 operation, the unit handles up to 12 A at 230 V and 12 A at 400 V, 9 A at 500 V, with 3.5 A at 690 V (NO). For AC-1, ratings reach 12 A at 220/240 V and 12 A at 380/440 V, dropping to 6 A at 690 V. The rated power for AC-3 is 3 kW at 230 V and 5.5 kW at 400/500 V, with 3 kW at 690 V NO.
Yes. The coil voltage is 48 V DC with a rated control circuit voltage (Uc) of 48 V DC. Coil operating limits follow IEC 60947-4-1: 0.85 to 1.1 times Uc at temperatures up to 55 °C. Coil consumption is 3.5 W, enabling energy-efficient, low-heat operation in building automation and machine control systems.
The device carries IEC/EN 60947-1, IEC/EN 60947-4-1, and IEC/EN 60947-5-1 certifications, along with UL 60947-1 and UL 60947-4-1, CE/UKCA declarations, and other conducting standards like CB/EAC. This ensures global compliance for cross-border projects, automotive and non-automotive applications, and straightforward procurement for regulated environments.
With a mechanical durability of 10,000,000 cycles and low coil power (3.5 W), the unit reduces replacement frequency and energy consumption. Its compact 47.5 × 47.7 × 45.2 mm footprint eases space constraints, while soldering-pin terminals simplify field wiring. Together, these factors translate to lower total cost of ownership and faster commissioning in building automation and small industrial systems.