ABB GJL1313009R5101 Mini Contactor - UL Certified

Part Number: GJL1313009R5101
Manufacturer
ABB
Part number
GJL1313009R5101

Quick Summary

ABB GJL1313009R5101 Mini Contactor provides reliable 3-pole load switching for automation and building systems. It addresses space constraints in control panels by offering a compact footprint and low coil consumption that enables direct PLC control. Certified to IEC/EN 60947-1 and 60947-4-1, UL/CSA, CE and UKCA, it also carries RoHS compliance and IP20 protection for safe, compliant installations. Ideal for DIN rail mounting (TH35-15/TH35-7.5) in commercial and light industrial environments, the device supports 690 V mains and 12 A AC-3 ratings, delivering a practical combination of performance and cost efficiency for automation projects.

Product Information

Extended Description

GJL1313009R5101 ABB: The BC7-30-10-P mini contactor is a compact 3 pole contactor with 1 auxiliary contact and soldering pins. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 12 A (AC-1) or switching of control signals. Due to the low coil consumption, this device can be directly controlled by a PLC. Further features are the noiseless and hum-free coil and a switch position indication.
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
2CDC102047M6801
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing - B6 / BC6 / B7 / BC7 / K6 / KC6 (-P)
Product Net Width
47.5 mm
Product Net Depth / Length
47.7 mm
Product Net Height
45.2 mm
Product Net Weight
0.17 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1 | UL 60947-1 | UL 60947-4-1 | IEC 60335-2-40 A2L
Rated Operational Voltage
Auxiliary Circuit 690 V AC | Auxiliary Circuit 250 V DC | Main Circuit 690 V AC | Main Circuit 220 V DC
Rated Frequency (f)
Control Circuit DC | Main Circuit 60 Hz | Main Circuit 50 Hz | Main Circuit DC
Conventional Free-air Thermal Current (Ith)
Main Circuit 12 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 40 °C 12 A | (220 / 240 V) 55 °C 12 A | (380 / 440 V) 40 °C 12 A | (380 / 440 V) 55 °C 12 A | (690 V) 40 °C 6 A | (690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)
(230 V) 55°C 12 A | (400 V) 55 °C 12 A | (500 V) 55 °C 9 A | (690 V) NO 55°C 3.5 A
Rated Operational Current AC-15 (Ie)
(24 V) 4 A | (120 V) 4 A | (500 V) 2 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 2.5 A | (110 V) 0.7 A | (220 / 240 V) 0.4 A
Rated Operational Power AC-3 (Pe)
(230 V) Three Phase 3 kW | (400 V) Three Phase 5.5 kW | (500 V) Three Phase 5.5 kW | (690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-3
8 x Ie / AC-3
Rated Making Capacity AC-3
10 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)
690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV | Main Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-15) 600 cycles per hour | (AC-3) 600 cycles per hour | (DC-1) 600 cycles per hour | (DC-13) 600 cycles per hour | (DC-3) 600 cycles per hour
Mechanical Durability
Nr. Operations 10000000 cycle
Minimum Switching Capacity
Auxiliary Circuit 17 V | Auxiliary Circuit 5 mA
Coil Operating Limits
(acc. to IEC 60947-4-1) for DC supply Uc Min. ... Uc Max. (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)
17 ... 32 V DC
Coil Consumption
Average Holding Value DC 2.4 W | Average Pull-in Value DC 2.4 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of Protection
Auxiliary Circuit Terminals IP20 | Control Circuit Terminals IP20 | Main Circuit Terminals IP20
Terminal Type
Soldering Pins
Mini Contactor Type
Interface Mini Contactor
Product Name
Mini Contactor
Remarks
No CA6 or CAF6 mountable
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
General Use Rating UL/CSA
(600 V AC) 12 A
Horsepower Rating UL/CSA
(115 V AC) Single Phase 0.75 Hp | (200 V AC) Three Phase 2 Hp | (220 ... 240 V AC) Three Phase 3 Hp | (230 V AC) Single Phase 1.5 Hp | (440 ... 480 V AC) Three Phase 5 Hp | (550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSA
A600
Full Load Amps Motor Use
(115 V AC) Single Phase 13.8 A | (200 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 9.6 A | (230 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 6.1 A
Ambient Air Temperature
Operation -20 ... +55 °C | Storage -40 ... +80 °C
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to Vibrations
5g 5 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End Of Life Instruction B(C)6-P, B(C)7-P, K(C)6-P, VB(C)6-P, VB(C)7-P
Environmental Product Declaration - EPD
Environmental Product Declaration PEP B(C)6, B(C)7 (EN)
A2L Certificate – IEC
A2L Certificate - B6-, B7-, K6- series, CA6, CAF6 - Mini Contactor
BV Certificate
BV Certificate - ESB24, ESB40, ESB63, EH04, B6, B7, EH04 - Installation Contactor
CB Certificate
CB Certificate - B6, BC6, VB6, VBC6, B7, BC7, VB7, VBC7 - Mini Contactor
CQC Certificate
CQC Certificate, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
cURus Certificate
cUL_E191658
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, B6,BC6,B7,BC7,VB6,VBC6,VB7,VBC7, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
Declaration of Conformity - UKCA
UK Declaration of Conformity - B6, B7, K6, VB6, VB7, TBC7, TKC6 - Mini Contactor
DNV GL Certificate
DNV Certificate - B6, B7 - Mini Contactor
EAC Certificate
EAC Certificate - B6, BC6, B6S, VB6,B7, BC7, B7D, B7S, VB7, TBC7, ESB24, EN24, ESB40, EN40, ESB63 - Contactors
KC Certificate
KC Certificate - B6, B7
LR Certificate
LR Certificate - B6, B7 - Mini Contactor
RMRS Certificate
RMRS Certificate - B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 - Mini Contactor
UL Certificate
UL Certificate of Compliance - B6, B7 (Pin/Faston) - Mini Contactor
Package Level 1 Units
box 10 piece
Package Level 1 Width
108 mm
Package Level 1 Depth / Length
247 mm
Package Level 1 Height
69 mm
Package Level 1 Gross Weight
1.775 kg
Package Level 1 EAN
4013614418778
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
Feature: Low coil consumption (2.4 W) at 17–32 V DC. Business Impact: Enables PLC direct control and reduces energised hold-in losses, lowering panel heat and wiring complexity. Application: Ideal for compact control panels and energy-efficient machine control. Feature: 3 NO main contacts + 1 NO auxiliary contact. Business Impact: Simplifies wiring schemes and expands control options, improving startup sequencing and fault handling. Application: Conveyor lines and miniature motor control where compact control is essential. Feature: Soldering pin terminals. Business Impact: Ensures robust PCB mounting and reliable long-term connections, reducing field maintenance. Application: Integrated control electronics in compact automation assemblies. Feature: DIN rail mounting compatibility (TH35-15/TH35-7.5). Business Impact: Simplifies installation, enhances modularity, and accelerates panel assembly. Application: Standard industrial enclosures and building automation panels. Feature: IP20 protection for terminals. Business Impact: Improves reliability in non-harsh environments while supporting easy accessibility for maintenance. Application: Indoor electrical cabinets and control panels. Feature: Mechanical durability rated at 10 million cycles. Business Impact: Delivers proven longevity, lowering replacement costs and downtime. Application: Continuous operation equipment and high-cycle automation tasks. Feature: Rated power and voltage for AC-3 loads up to 5.5 kW at 400–500 V. Business Impact: Supports efficient motor control and compliant switching, reducing energy waste. Application: Medium-power drive applications in commercial and light industrial settings.

Get a Quick Quote for a ABB GJL1313009R5101

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB GJL1313009R5101? Enquire Now

FAQs

This mini contactor supports DIN rail mounting (TH35-15 and TH35-7.5) for quick, modular installations. It also features soldering pin terminals for PCB mounting, offering flexible integration into control panels and machine controls. The compact dimensions (47.5 mm W, 47.7 mm D, 45.2 mm H) enable tight panel layouts.
Yes. The device provides AC-3 ratings up to 5.5 kW at 400–500 V and 12 A at 230–690 V depending on the voltage, making it suitable for switching medium-power 3-phase motors. It combines compact size with robust switching capability for reliable motor control.
The coil voltage range is 17–32 V DC, ideal for direct PLC control. The coil power is 2.4 W for both pull-in and holding, which minimizes heat generation and reduces energy consumption in control circuits.
The product complies with IEC/EN 60947-1 and 60947-4-1, and carries UL/CSA recognitions, CE and UKCA declarations, RoHS compliance, and IP20 protection. These certifications support safe, compliant installations across global markets.
It is designed for DIN rail mounting (TH35-15/TH35-7.5) and provides IP20 protection for terminals, simplifying maintenance while preserving safe operation inside control panels. The compact form factor also reduces footprint and wiring complexity in new builds and retrofits.