Eaton LG3600WS01 Molded Case Circuit Breaker - UL 489/CSA/IEC 947-2

Part Number: LG3600WS01
Manufacturer
Eaton
Part number
LG3600WS01

Quick Summary

LG3600WS01 molded case circuit breaker provides precise overcurrent protection for engine-generator power systems. When downtime and unexpected trips threaten critical operations, reliable protection and fast response are essential. This Eaton Series C MCCB carries UL 489, CSA C22.2 No. 5, and IEC 947-2 certifications, underscoring safety and global compliance. Three-pole, L-frame construction with fixed thermal and magnetic trips covers a broad range (600–2500 A) and 600 Vac service, while a 12–24 Vac/dc shunt trip on the same side with left pigtail supports remote actuation. Designed for rugged industrial environments, it simplifies stocking, enables easy installation in standard MCCB enclosures, and pairs with generator ratings up to 542 kVA at 600 Vac for scalable power protection.

Product Information

Extended Description

LG3600WS01 Eaton: Eaton Series C complete molded case circuit breaker, L-frame, Fixed thermal and magnetic trips, 600-2500A, Three-pole, 600A, 600 Vac, No term., Engine generator, 12-24 Vac/dc same side w/ left pigtail, Reverse feed
Product Name
Eaton Series C complete molded case circuit breaker
Catalog Number
LG3600WS01
UPC
782116977680
Product Length/Depth
5.48 in
Product Height
5.48 in
Product Width
5.48 in
Product Weight
16 lb
Warranty
Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Certifications
UL 489 CSA Std. C22.2 No. 5 IEC 947-2
Amperage Rating
600 A
Voltage rating
600 Vac
Trip Type
T186
Circuit breaker frame type
Complete breaker
Series
Series C
Shunt trip
12-24 Vac/dc same side with left pigtail shunt
Terminals
Without terminals
Frame
L
Class
Engine generator
Generator rating
217 kVA/173 kW at 240 Vac, 433 kVA/347 kW at 240 Vac, 542 kVA/433 kW at 600 Vac
Number of poles
Three-pole
Trip rating
600-2500 A
Functions
Reverse
Feature: Three-pole, L-frame Series C complete molded case breaker provides compact, standardized protection for high-current circuits. Benefit: Fits easily in common MCCB enclosures, reduces spare parts diversity, and streamlines panel design in industrial power distribution. Application: Ideal for engine-generator protection and critical load circuits in manufacturing plants. Feature: Fixed thermal and magnetic trips deliver predictable, fast interruption with consistent coordination. Benefit: Minimizes nuisance trips and protects generator sets and motors, improving uptime and extending equipment life. Application: Main protection for heavy-duty power rails and generator bus connections where reliability is non-negotiable. Feature: Shunt trip option 12-24 Vac/dc with left-pigtail enables remote shutdown and safety interlocks. Benefit: Enhances plant safety and compliance with remote de-energization protocols. Application: Emergency stopping, safety interlocks, and generator sequencing in critical facilities. Feature: Generator ratings up to 542 kVA/433 kW at 600 Vac and 217 kVA/173 kW at 240 Vac. Benefit: Supports large generator sets and scalable power protection across diverse applications. Application: Power generation, standby power systems, and heavy machinery protection. Feature: Terminals are not included; field-installed terminals or lugs allow flexible integration. Benefit: Enables tailored wiring schemes and compatibility with existing electrical infrastructure. Application: Retrofit projects and custom panel builds where terminal options vary by installation. Feature: Certifications UL 489, CSA, IEC 947-2 and Eaton warranty. Benefit: Ensures global compliance and a clear service lifecycle, reducing total cost of ownership. Application: Global deployments and long-term maintenance planning in industrial facilities.

Get a Quick Quote for a Eaton LG3600WS01

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in Eaton LG3600WS01? Enquire Now

FAQs

LG3600WS01 is a Series C three-pole MCCB designed for standard MCCB enclosures. The unit ships without terminals, so compatible field-installed lugs or terminals from Eaton or approved third parties must be selected to match enclosure dimensions and wire schedules. It fits common L-frame, 3-pole configurations used in industrial power distributions.
The breaker provides a 600 A current rating with a 600 Vac voltage rating and a Trip Type of T186. It is a three-pole device with an L-frame, part of the Series C family, and is designed for fixed thermal and magnetic trips to ensure fast, reliable interruption in motor and generator circuits.
Yes. The unit is explicitly specified for engine-generator protection, offering generator ratings up to 542 kVA/433 kW at 600 Vac (and 217 kVA/173 kW at 240 Vac). It also supports a shunt trip (12–24 Vac/dc, same side, left-pigtail) enabling remote trip and safe reverse-feed control in protective schemes.
LG3600WS01 carries UL 489, CSA C22.2 No. 5, and IEC 947-2 certifications. These credentials confirm compliance with global electrical safety and performance standards, facilitating regulatory approvals, international projects, and consistent cross-border sourcing.
Eaton provides a one-year warranty from installation or an 18-month window from shipment (whichever comes first) per policy 25-000. In addition, authorized Breaker Service Centers offer maintenance and replacement support, helping minimize downtime and extend system reliability.