Eaton P3BFDC3080 Pow-R-Way III Breaker - UL 857
Part Number: P3BFDC3080
Quick Summary
Pow-R-Way III circuit breaker plug-in unit protects busway power distribution systems with rapid, reliable fault isolation. In high-density manufacturing environments, retrofitting or upgrading breakers can disrupt lines and raise safety risk; this plug-in unit simplifies installation and maintenance. It carries IEEE Certified, CSA Certified, ANSI, and UL 857 listings to ensure regulatory compliance and protective coordination. Designed for modular expansion, it supports 3-pole, 80A protection within the Pow-R-Way busway family, delivering consistent performance across zones. This solution aligns with modern electrical distribution needs, offering scalable protection, easy integration with existing equipment, and clear return-on-asset value for industrial facilities and engineering teams.
Product Information
Extended Description
P3BFDC3080 Eaton: Pow-R-Way III Busway, Circuit Breaker Plug-in Unit, 3-Pole, 80 AMP, FDC Frame Type
Product Name
Eaton Pow-R-Way III circuit breaker plug-in unit
Catalog Number
P3BFDC3080
UPC
786683008211
Product Length/Depth
12.36 in
Product Height
21.2 in
Product Width
5.43 in
Product Weight
25 lb
Compliances
NEMA Compliant
Certifications
IEEE Certified CSA Certified ANSI UL 857
Circuit Breaker Frame
F
Grounding Options
50% Integral/Housing
Type
Breaker
Amperage Rating
80A
Interrupt rating
200 kAIC at 240 Vac, 100 kAIC at 480 Vac, 35 kAIC at 600 Vac
Feature: 3-Pole, 80A plug-in unit with an F frame.Business Impact: Provides targeted protection in a compact footprint, enabling quick swaps and minimizing busway downtime.Application: Ideal for Eaton Pow-R-Way III busway configurations in distribution feeders and line-side protection. Feature: High interrupt rating of 200 kAIC at 240V, 100 kAIC at 480V, and 35 kAIC at 600V.Business Impact: Improves fault tolerance and downstream equipment protection, reducing risk of collateral damage during faults.Application: Suitable for medium- to high-load industrial circuits with diverse voltage profiles. Feature: Grounding Options with 50% Integral/Housing grounding.Business Impact: Simplifies grounding schemes and reduces field wiring complexity, speeding up installation.Application: Fits standard Pow-R-Way busway grounding practices in integrated systems. Feature: Compliance and certifications—NEMA Compliant; IEEE Certified; CSA Certified; ANSI; UL 857.Business Impact: Ensures regulatory alignment and safety approvals, lowering compliance risk for audits and inspections.Application: Any regulated industrial environment requiring proven protective coordination. Feature: Precise dimensions and weight—12.36 in L, 21.2 in H, 5.43 in W; 25 lb.Business Impact: Eases space planning, panel layout, and retrofit projects while maintaining robust protection.Application: Retrofit or new-build busway installations where space is at a premium.
Get a Quick Quote for a Eaton P3BFDC3080
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in Eaton P3BFDC3080?
Enquire Now
FAQs
The P3BFDC3080 is a 3-pole, 80A plug-in breaker designed specifically for Pow-R-Way III busways. Its F frame and 50% integral grounding option streamline mounting and grounding within standard Eaton busway configurations, enabling quick swaps and minimal service interruption during upgrades or expansions.
The unit provides 200 kAIC interrupt rating at 240V, 100 kAIC at 480V, and 35 kAIC at 600V. This makes it suitable for diverse industrial loads, including motors and other high-impedance equipment, while maintaining strong fault protection across typical busway circuits.
This model carries IEEE Certified, CSA Certified, ANSI, and UL 857 listings and is NEMA compliant, ensuring regulatory alignment, protective coordination, and robust safety validation for industrial installations.
By offering plug-in replacement, modular expansion, and a compact footprint, it reduces downtime during maintenance, lowers field wiring complexity, and provides reliable protection with long service life—translating to lower maintenance costs and higher asset uptime over the system’s life.
The device measures 12.36 inches in depth, 21.2 inches in height, and 5.43 inches in width, with an approximate weight of 25 pounds. These specs support accurate space planning for retrofit and new-build busway installations.