Eaton SPD080480D3C Surge Protection Device - UL 1449

Part Number: SPD080480D3C
Manufacturer
Eaton
Part number
SPD080480D3C

Quick Summary

The Eaton SPD080480D3C surge protection device protects switchboards, panelboards, and busways from damaging transient surges in 480V delta systems. End users often face unpredictable lightning and switching surges that accelerate equipment wear, trigger outages, and shorten asset life. This unit carries UL 1449 Listed certification and combines EMI/RFI filtering with an audible alarm, a Form C relay contact, and a built-in surge counter for real-time protection visibility. Designed for seamless integration with PRL series installations, it delivers reliable, low-maintenance protection with a compact footprint. By combining robust electrical protection with monitoring features, the SPD080480D3C helps facilities meet reliability targets while simplifying compliance and ongoing maintenance.

Product Information

Extended Description

SPD080480D3C Eaton: Eaton Surge Protection Device, SPD Series, 80 kA per phase, 480V delta (3W+G) rating, 640 L-G, 640 L-L MCOV, Internal integrated, and surge counter, used with Switchboard, busways, and panel boards (PRL1a, 2a, 3a, 3e, 4)
Product Name
Eaton SPD series surge protection device
Catalog Number
SPD080480D3C
UPC
786685321684
Product Length/Depth
9.5 in
Product Height
3.45 in
Product Width
5.4 in
Product Weight
3.5 lb
Warranty
15 year
Certifications
UL 1449 UL Listed
Type
SPD
Special features
Meets or exceeds the requirements specified in IBC ®2006, CBC2007, and UBC®Zone 4. Audible alarm with silence button. Form C relay contact. EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz. Surge counter with rest button
Accessories
Standard feature package and surge counter
Frequency rating
50/60 Hz
Interrupt rating
200 kAIC
Nominal Discharge Current
20 kA
Operating voltage
640 L-G, 640 L-L
Used with
Switchboard, busways, and panelboards (PRL1a, 2a, 3a, 3e, 4)
Voltage rating
480 delta (3W+G)
Surge current
80 kA per phase
Short-circuit rating
200 kA
Operating temperature
-40 to 50 °C
Mounting Method
Internal integrated
Feature: 80 kA per phase surge capability with 640 V L-G and L-L ratings. Business Impact: Withstands high-energy events common in industrial environments, reducing the chance of equipment damage and unplanned downtime. Application: Ideal for 480V delta systems in switchboards, busways, and panelboards. The installation benefits include robust protection without complex wiring, supporting faster commissioning and easier upgrades. Feature: EMI/RFI filtering up to 50 dB across 10 kHz to 100 MHz. Business Impact: Cleaner electrical signals improve PLC/drive performance and extend life of downstream components. Application: Critical where sensitive electronics co-exist with heavy motors. Feature: Audible alarm with silence button and Form C relay, plus a surge counter with rest button. Business Impact: Immediate fault indication and traceability for maintenance planning, improving response times. Application: Centralized protection with optional remote monitoring. Feature: Internal integrated mounting and compact footprint (9.5 in L × 5.4 in W × 3.45 in H), 3.5 lb weight. Business Impact: Simplifies installation in tight spaces, reduces panel crowding, and speeds retrofits. Application: Panelboards and switchgear where space is at a premium. Feature: 15-year warranty and UL 1449 Listed certification. Business Impact: Long-term asset protection with regulatory alignment, lowering life-cycle costs. Application: Offshore, manufacturing, and process environments requiring proven reliability.

Get a Quick Quote for a Eaton SPD080480D3C

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in Eaton SPD080480D3C? Enquire Now

FAQs

Begin by verifying system voltage and confirming a 480V delta configuration. Mount the device using its internal integrated mounting method in a suitable enclosure, ensuring clearance for heat dissipation. Connect line-side and load-side conductors per Eaton’s wiring diagram, and wire the Form C relay and audible alarm to the panel’s monitoring network as required. After installation, perform a functional test and confer with your panel schedule to confirm correct integration with the PRL series devices.
80 kA per phase is the maximum surge current the device can safely conduct per phase without sustaining damage. This rating correlates to the energy level typical of industrial transients. For sizing, compare expected surge energy in your location and equipment, and design factors such as service entrance protection and downstream devices. A higher per-phase rating generally indicates greater protection margin for high-energy environments, reducing the risk of upstream component failure.
Yes, the SPD080480D3C is designed for use with switchboards, busways, and panelboards including PRL1a, PRL2a, PRL3a, PRL3e, and PRL4 variants. Its internal mounting and compact footprint simplify integration into existing enclosures, while the built-in surge counter and audible alarm provide proactive protection monitoring. Always verify the exact PRL configuration and follow Eaton’s installation guide for wiring and clearance requirements.
The unit is UL 1449 Listed, indicating compliance with recognized surge protection system safety standards. This certification provides confidence in performance under surge conditions and supports regulatory and insurance requirements for electrical installations. UL 1449 Listing is particularly important for mission-critical applications, ensuring consistent surge mitigation and protection feature performance over the device’s 15-year warranty period.
The SPD080480D3C includes a built-in surge counter with a rest button, enabling real-time monitoring of surge activity and easier preventive maintenance planning. This visibility helps justify ROI by enabling targeted replacements before failures occur, reducing unexpected downtime and extending equipment life. The audible alarm also provides immediate fault notification, supporting fast technician response and lower overall maintenance costs.