Eaton SPD100600D1J Surge Protection Device - UL Listed
Part Number: SPD100600D1J
Quick Summary
The Eaton SPD100600D1J surge protection device protects MCCs from transient voltage spikes. This helps prevent motor wear, nuisance trips, and unexpected downtime that erodes uptime and productivity. UL 1449 Listed certification and UL Listed status, along with compliance to IBC/CBC/UBC Zone 4 standards, provide robust regulatory confidence. By adding EMI/RFI filtering and an audible alarm with a silence button, this SPD strengthens electrical system resilience while supporting easy maintenance and procurement efficiency. The unit is designed for motor control centers, delivering reliable transient protection with a compact form and a warranty that aligns with facility reliability programs.
Product Information
Extended Description
SPD100600D1J Eaton: Eaton Surge Protection Device, SPD Series, 100 kA per phase, 600V delta (4W+G) rating, 840 L-G, 840 L-L MCOV, Internal integrated, Basic feature package, used with Motor control centers
Product Name
Eaton SPD series surge protection device
Catalog Number
SPD100600D1J
UPC
786685324500
Product Length/Depth
9.5 in
Product Height
3.45 in
Product Width
5.4 in
Product Weight
3.5 lb
Warranty
15 year
Certifications
UL 1449 UL Listed
Type
SPD
Special features
Meets or exceeds the requirements specified in IBC ®2006, CBC2007, and UBC®Zone 4. Audible alarm with silence button. Form C relay contact. EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz. Surge counter with rest button
Accessories
Basic feature package
Frequency rating
50/60 Hz
Interrupt rating
200 kAIC
Nominal Discharge Current
20 kA
Operating voltage
840 L-G, 840 L-L
Used with
Motor control centers
Voltage rating
600 delta (4W+G)
Surge current
100 kA per phase
Short-circuit rating
200 kA
Operating temperature
-40 to 50 °C
Mounting Method
Internal integrated
Feature: High surge capability up to 100 kA per phase with a 200 kAIC short-circuit rating. Business Impact: Delivers strong transient protection to MCCs, reducing motor insulation stress and prolonging equipment life. Application: Suitable for motor control centers in demanding plant environments. Feature: 600 V delta (4W+G) voltage rating with 840 L-G and 840 L-L MCOV. Business Impact: Enables reliable peak protection across typical three-phase delta systems, minimizing nuisance trips and protecting sensitive drives. Application: Industrial facilities employing delta-connected MCCs. Feature: EMI/RFI filtering delivering up to 50 dB attenuation from 10 kHz to 100 MHz. Business Impact: Improves supply quality for control logic and drives, lowering EMI-related faults and improving PLC performance. Application: Modern MCCs with sensitive control circuits. Feature: Built-in audible alarm, silence button, and Form C relay contact. Business Impact: Enables immediate fault awareness and remote signaling to plant automation, supporting quick operator response. Application: Safety-critical installations where quick diagnostics are essential. Feature: Surge counter with rest button and basic feature package. Business Impact: Provides traceable surge events for maintenance planning and warranty validation, reducing unplanned downtime. Application: Preventive maintenance programs in manufacturing facilities. Feature: Internal integrated mounting and compact footprint. Business Impact: Simplifies installation inside MCCs, reduces enclosure space, and lowers installation labor costs. Application: Retrofit and new MCC builds across industrial plants. Feature: 15-year warranty and UL 1449 UL Listed certifications. Business Impact: Long-term asset protection and regulatory confidence, supporting total cost of ownership goals. Application: Compliance-focused facilities and OEMs.
Get a Quick Quote for a Eaton SPD100600D1J
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in Eaton SPD100600D1J?
Enquire Now
FAQs
Begin by verifying the MCC duct and space for internal mounting. The SPD100600D1J supports internal integration, and its basic feature package simplifies wiring with standard connections. Mount the unit inside the MCC using the built-in mounting points, connect the line and load terminals per the 600 V delta configuration, and connect the Form C relay and alarm circuit to your PLC or annunciation system. Always follow local codes and Eaton’s installation sheet for best results.
Key specs to confirm include a 100 kA per phase surge current rating, 200 kAIC short-circuit rating, 600 V delta (4W+G) voltage rating, 840 V line-to-ground and line-to-line MCOV, frequency compatibility at 50/60 Hz, and a -40 to 50 °C operating range. Also confirm UL 1449 Listed certification and EMI/RFI filtering performance up to 50 dB from 10 kHz to 100 MHz to ensure control logic integrity.
Yes. It is designed for motor control centers and includes features like EMI/RFI filtering, a robust surge counter, and a silence-enabled audible alarm to aid maintenance teams. The unit’s -40 to 50 °C operating range and UL certification provide confidence in reliability across typical industrial environments, making it fit for factory floors and process plants.
The SPD100600D1J carries UL 1449 Listed certification and UL Listed status, ensuring recognized protection against transient events. In addition, it aligns with safety and construction standards referenced by IBC, CBC, and UBC Zone 4 in its special features, supporting regulatory compliance and safer MCC operation.
The 15-year warranty reduces lifecycle risk and replacement costs, while built-in surge counting supports proactive maintenance. EMI/RFI filtering improves system reliability by reducing nuisance faults in drives and PLCs, and the audible alarm plus Form C relay enhances fast fault localization. Together, these features help minimize downtime and extend MCC life.