Eaton X48M28T12CUEENON Harmonic mitigating transformer - UL Listed
Part Number: X48M28T12CUEENON
Quick Summary
The Eaton Harmonic mitigating transformer X48M28T12CUEENON delivers clean, balanced power for three-phase 480 V systems. Engineers often battle harmonic distortion, overheating, and unpredictable downtime when power quality isn’t managed effectively. This unit is UL Listed, NEMA TP-1 Compliant, and designed for a 150 °C rise with a 200 °C insulation system, offering robust protection. With copper windings, a dry-type construction, and a rugged frame, it supports reliable installations in space-constrained facilities. Coupled with a 112.5 kVA rating and practical taps, it translates to lower maintenance costs and better energy efficiency for manufacturers, data centers, and industrial facilities alike.
Product Information
Extended Description
X48M28T12CUEENON Eaton: Eaton Harmonic mitigating transformer, PV 480V, Taps: 2 at +2.5% /4 at -2.5%, SV 208Y/120V, 150°C rise w/ 200°C insulation systeam, 112.5 kVA, Copper windings, EE, NON
Product Name
Eaton Harmonic mitigating transformer
Catalog Number
X48M28T12CUEENON
UPC
786680030000
Product Length/Depth
24.67 in
Product Height
56.17 in
Product Width
31.44 in
Product Weight
1459 lb
Warranty
Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Compliances
NEMA TP-1 Compliant
Certifications
UL Listed
Catalog Notes
NEMA TP-1 efficient
Coil material
Copper
Frame
917
Tap size
2 at +2.5% FCAN, 4 at -2.5% FCBN
Type
Dry Type Distribution Transformer
Wiring connection
200X
Frequency rating
60 Hz
Phase
Three-phase
Phase shift
0 °
Primary voltage
480 V
Secondary Voltage
208 Y/120 V
Temperature rise
150 °C rise
Volt ampere rating
112.5 kVA
Special features
Electrostatically shielded
Weathershield
WS34
Feature: copper windings. Business Impact: reduced resistance and lower I²R losses translate to improved efficiency and cooler operation under load. Application: ideal for continuous-duty distribution in manufacturing lines and critical power panels. Feature: dry-type insulation. Business Impact: safer operation in indoor spaces and easier maintenance with lower fire risk. Application: suitable for retrofits and new builds in industrial plants where classroom or office proximity demands safer electrical equipment. Feature: 60 Hz three-phase operation. Business Impact: compatible with common regional grids, enabling stable voltage delivery and predictable performance. Application: supports data centers and multi-line manufacturing processes requiring synchronized power. Feature: taps at +2.5% and -2.5%. Business Impact: voltage fine‑tuning reduces voltage sag/overvoltage, protecting sensitive loads and extending equipment life. Application: critical feeders and machine control panels in variable supply environments. Feature: frame 917 with 31.44 in width and 56.17 in height. Business Impact: compact footprint for crowded electrical rooms while maintaining robust cooling and service access. Application: retrofit projects in retrofit or new installations where space is at a premium. Feature: 112.5 kVA rating and 480 V to 208 Y/120 V secondary. Business Impact: supports multiple heavy loads with clean, balanced power and efficient energy use. Application: distribution transformers feeding PLCs, drives, and control systems in industrial facilities. Feature: Weathershield WS34 and electrostatically shielded design. Business Impact: enhanced protection against environmental exposure and interference, reducing maintenance cycles. Application: outdoor or harsh-environment locations and installations near high-EMI equipment.
Get a Quick Quote for a Eaton X48M28T12CUEENON
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in Eaton X48M28T12CUEENON?
Enquire Now
FAQs
To install the Eaton X48M28T12CUEENON, verify a three-phase 480 V service with a 60 Hz supply and plan for a 112.5 kVA load. Ensure cooling, electrical room clearance, and access to the dry-type transformer for servicing. The unit’s frame 917 footprint and copper windings support robust operation, while the WS34 weather shield aids outdoor readiness when applicable.
This transformer is UL Listed and NEMA TP-1 Compliant, with NEMA TP-1 efficient catalog notes. These certifications indicate compliance with safety and efficiency standards, enabling easier code approvals, reduced risk of liability, and predictable long-term operating costs—critical factors for data centers, manufacturing floors, and commercial facilities.
Yes. With a 112.5 kVA rating, 480 V primary, 208Y/120 V secondary, and a three-phase 60 Hz design, the unit delivers clean power to sensitive loads like servers and drives. The copper windings and electrostatic shielding further minimize interference, while the taps allow voltage fine‑tuning to maintain stable rack and process operation.
Key specs include 112.5 kVA rating, 480 V primary, 208Y/120 V secondary, 60 Hz, and 2 taps at +2.5% plus 4 taps at -2.5%. The 150 °C rise with a 200 °C insulation system supports demanding environments, while copper windings deliver high efficiency and lower thermal stress—translating to reduced cooling costs and longer service life.
Maintenance benefits stem from dry-type construction, which reduces fire risk and simplifies inspection. The UL Listing and NEMA TP-1 compliance provide regulatory confidence, while the efficient NEMA TP-1 notes help lower energy waste. Over time, improved power quality reduces downtime and extends equipment life, delivering a favorable return on investment for industrial facilities.