Eaton Z48G28B45 Transformer - UL Listed Hazardous Location

Part Number: Z48G28B45
Manufacturer
Eaton
Part number
Z48G28B45

Quick Summary

Z48G28B45 Transformer from Eaton provides hazardous-location step-down power for 480 V to 208Y/120 V in Class 1 Division 2 areas. Facility teams often face safety compliance, installation delays, and ongoing maintenance costs when selecting power transformers for harsh environments. It carries UL Listed certification, Class 1 Division 2 Groups C and D rating, and a NEMA 3R enclosure for reliable indoor-outdoor service. For industrial automation and hazardous-location applications, it pairs with broader Eaton power-management tools to improve uptime and efficiency. The design supports straightforward installation, reduced phasing risk, and predictable thermal performance in demanding settings. Engineered for repeatable results, the Z48G28B45 minimizes outages and supports uptime targets across mission-critical drives and instrumentation.

Product Information

Extended Description

Z48G28B45 Eaton: Class 1 Division 2 Groups C and D, Hazardous Location Transformer, EPTZ, 3PH, Primary Voltage: 480V, Taps: 2 at -5% FCBN, Secondary Voltage: 208Y/120V, 80°C, 45 kVA, Al windings, Frame: 245H, Indoor-Outdoor
Product Name
Eaton Hazardous location encapsulated transformer
Catalog Number
Z48G28B45
UPC
786680091582
Product Length/Depth
15.68 in
Product Height
31.98 in
Product Width
46.23 in
Product Weight
1230 lb
Warranty
Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Certifications
UL Listed
Type
Class 1 Division 2 Groups C and D, Hazardous Location Transformer
Coil material
Aluminum
Frequency rating
60 Hz
Phase
Three-phase
Primary voltage
480 V
Secondary Voltage
208Y/120 V
Temperature rise
80 °C rise
Design
EPTZ
Enclosure
NEMA 3R
Frame
245H
Tap size
2 at -5% FCBN
Volt ampere rating
45 kVA
Weathershield
Indoor-Outdoor
Wiring connection
66A
Encapsulated hazardous-location design provides safety and reliability. The encapsulation reduces moisture intrusion and arcing potential, translating to lower risk and simplified compliance for Class I Division 2 environments. Applications include oil and gas facilities, chemical plants, and mining operations where outages are costly and safety standards are strict. Three-phase 480 V primary to 208Y/120 V secondary with a 45 kVA rating and 60 Hz frequency gives stable power for controls and drives. The -5% FCBN two-tap feature lets technicians compensate for supply variations without swapping components, reducing installation time and voltage-related issues. Aluminum windings and an 80°C temperature rise support robust heat management in a rugged frame 245H with a NEMA 3R enclosure for indoor-outdoor service. Weather tolerance and Weathershield Indoors-Outdoor design, plus a 66A wiring connection, support straightforward integration with existing switchgear and panels. Warranty and service details—Eaton’s 25-000 policy offers one year from installation or 18 months from shipment—help reduce lifecycle risk and sustain uptime across a broad range of industrial environments.

Get a Quick Quote for a Eaton Z48G28B45

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in Eaton Z48G28B45? Enquire Now

FAQs

Ensure compliance with Class I Division 2 wiring practices and mount the transformer within the NEMA 3R enclosure for indoor-outdoor use. Verify 66A wiring connections, set the two taps at -5% FCBN as needed for supply variation, and deploy in well-ventilated, accessible spaces to facilitate maintenance and fault isolation.
The unit provides 45 kVA at a 480 V primary and 208Y/120 V secondary in a three-phase, 60 Hz system. Aluminum windings support efficient heat dissipation, while the 80 °C rise rating ensures reliable operation under elevated ambient temperatures common in industrial environments.
Yes. It is designed for Class 1 Division 2, Groups C and D environments, with UL Listed certification and a rugged NEMA 3R enclosure, making it well-suited for hazardous zones found in chemical processing, oil & gas, and related industries.
It carries UL Listed certification, Class 1 Division 2 Groups C and D ratings, and a NEMA 3R enclosure. These certifications verify safe operation in hazardous locations, ensure weather-resistant installation, and align with industry safety standards for industrial power distribution.
Warranty follows Eaton Selling Policy 25-000: one year from installation or eighteen months from shipment, whichever occurs first. Regular inspections, torque checks on terminations, and keeping the enclosure sealed against moisture will help sustain reliability and extend service life.