To wire a 3-phase motor, you must choose between Star or Delta based on your supply voltage and motor nameplate.
Star (High Voltage): Links W2-U2-V2 together. Use this for 400V mains on a standard 230/400V motor.
Delta (Low Voltage): Links U1-W2, V1-U2, W1-V2 in pairs. Use this for 230V inverter supply on a standard motor.
- Star (Y) Connection: Connects the three "finish" ends (W2, U2, V2) together. Used for 400V Supply on standard small/medium motors (up to 4.0kW).
- Delta (Δ) Connection: Connects the start of one phase to the end of the next (U1-W2, V1-U2, W1-V2). Used for 230V Supply (e.g., Single Phase Inverter) on small motors, OR 400V Supply on large motors (4kW+) marked 400/690V.
Star Connection - Wiring Diagram
.jpg)
Delta Connection - Wiring Diagram
.jpg)
** STOP: Check your motor nameplate.
- If it says 230/400V: Star = 400V (Mains), Delta = 230V (Inverter).
- If it says 400/690V: Delta = 400V (Mains), Star = 690V.